9-6 Air tight test and vacuum drying

The units were checked for leaks by the manufacturer.
Confirm that the valves are firmly closed before Air tight test or vacuum 
drying.
To prevent entry of any impurities and ensure sufficient pressure resis-
tance, always use the special tools dedicated for R410A.

Air tight test:

 Make sure to use nitrogen gas.

(For the service port location, refer to the 
“Caution” label attached on the front panel 
[right] of the outside unit.)

(Refer to figure)

1.

[Service precautions] Label

2.

Electrical components box lid

3.

[Caution] Label

Pressurize the liquid and gas pipes to 450 psi 
(do not pressurize more than 450 psi). If the 
pressure does not drop within 24 hours, the 
system passes the test. If the pressure drops, check where the nitro-
gen leaks from.

Vacuum drying:

 Use a vacuum pump which can evacuate to 

–14.6 psi.

1.

Evacuate the system from the liquid and gas pipes by using a 
vacuum pump for more than 2 hours and bring the system to 
–14.6 psi or less. After keeping the system under that condition 
for more than 1 hour, check if the vacuum gauge rises or not. If it 
rises, the system may either contain moisture inside or have 
leaks.

2.

Following should be executed if there is a possibility of moisture 
remaining inside the pipe (if piping work is carried out during the 
raining season or over a long period of time rainwater may enter 
the pipe during work).
After evacuating the system for 2 hours, pressurize the system to 
7.25 psi (vacuum break) with nitrogen gas and evacuate the sys-
tem again using the vacuum pump for 1 hour to –14.6 psi or less 
(vacuum drying). If the system cannot be evacuated to –14.6 psi 
within 2 hours, repeat the operation of vacuum break and vacuum 
drying.
Then, after leaving the system in vacuum for 1 hour, confirm that 
the vacuum gauge does not rise.

NOTE

Make sure to perform air tight test and vacuum drying using the service
ports of the stop valve shown in the table below.

9-7 Pipe insulation

After finishing the leak test and vacuum drying, the piping must be insu-
lated. Take into account the following points:

• Make sure to insulate the connection piping and refrigerant branch 

kits entirely. 

• Be sure to insulate the liquid-side, suction gas-side and discharge 

gas-side piping for the inter-unit piping and the refrigerant branch kits.
Not insulating them may cause leaking. (The gas piping can reach 
temperatures of 250 °F. Be sure the insulation used can withstand 
such temperatures.)

• If you think the humidity around the cooling piping might exceed

86 °F and RH80%, reinforce the insulation on the cooling piping (at 
least 13/16” thick). Condensation might form on the surface of the 
insulation.

• If there is a possibility that condensation on the stop valve might drip 

down into the indoor unit through gaps in the insulation and piping 
because the outside unit is located higher than the indoor unit, etc., 
this must be prevented by caulking the connections, etc.

WARNING

• Be sure to insulate connection piping, as touching them can cause 

burns.

9-8 Checking of device and installation conditions

Be sure to check the followings.

1.

Make sure there is no faulty power wiring or loosing of a nut. 
See “

8. FIELD WIRING

”.

2.

Make sure there is no faulty transmission wiring or loosing of a nut.
See “

8. FIELD WIRING

”.

3.

Make sure there is no faulty refrigerant piping. 
See “

9. REFRIGERANT PIPING

”.

4.

Make sure piping size is correct. 
See “

9-1 Selection of piping material

”.

5.

Make sure insulation work is done. 
See “

9-7 Pipe insulation

”.

6.

Make sure insulation resistance of main power circuit is not deterio-
rated. 
Using a megatester for 500V, check that the insulation resistance of 
2M

 or more is attained by applying a voltage of 500V DC between 

power terminals and earth. Never use the megatester for the trans-
mission wiring (between outside and indoor unit, outside and COOL/
HEAT selector and etc.).

9-9 Additional refrigerant charge

WARNING

• To avoid injury always use protective gloves and eye protection 

when charging refrigerant.

To avoid injury do not charge with unsuitable substances. Use only 
the appropriate refrigerant.

NOTE

Refrigerant cannot be charged until field wiring has been com-
pleted.
Refrigerant may only be charged after performing the leak test and
the vacuum drying (see above).
When charging a system, care shall be taken that its maximum per-
missible charge is never exceeded, in view of the danger of liquid
hammer.
Refrigerant containers shall be opened slowly.

TO AVOID COMPRESSOR BREAKDOWN. DO NOT CHARGE THE
REFRIGERANT MORE THAN THE SPECIFED AMOUNT TO RAISE
THE CONDENSING PRESSURE.

• This outside unit is factory charged with refrigerant and depending 

on pipe sizes and pipe lengths some systems require additional 
charging of refrigerant.

• Determine the amount of refrigerant to be added by referring to the 

table, write it down on the included “Added Refrigerant” plate and 
attach it to the rear side of the front cover.
Note: refer to the example of connection for the amount to be added.

Additional refrigerant charge procedure (1)-normally

• Charge the refrigerant to the liquid pipe in its liquid state. Since 

R410A is a mixed refrigerant, its composition changes if charged in 
a state of gas and normal system operation would no longer be 
assured.

• Make sure to use installation tools you exclusively use on R410A 

installations to withstand the pressure and to prevent foreign materi-
als from mixing into the system.

1.

Before charging, check whether the tank has a siphon attached or not.

How to charge with the siphon tank.

Other ways of charging with the tank.

One outside unit installed

Liquid line stop valve
Discharge gas line stop valve
Suction gas line stop valve

Multiple outside units installed

Liquid line stop valve
Discharge gas line stop valve
Suction gas line stop valve
Oil-equalizing line stop valve

1

3

2

There is a siphon tube
inside, so there is no need
to turn the tank upside-down.

Charge with the tank upright.

Charge with the tank upside-down.

Содержание RWEYQ144PTJU

Страница 1: ...for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de main pour r f rence ult rieure Ce manuel...

Страница 2: ...6 13 16 3 15 16 9 13 16 21 5 8 30 11 16 9 9 8 10 8 9 7 7 6 6 6 9 7 8 5 8 15 3 8 4 3 1 2 11 13 16 39 3 8 35 7 16 19 11 16 1 2 3 4 4 10 5 6 5 4 9 6 7 7 10 8 1 2 3 4 9 Heat recovery system Heat pump syst...

Страница 3: ...figure 13 figure 12 figure 11 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 6 1 2 7 C H SELECTOR TO IN D UNIT TO OUT D UNIT TO MULTI UNIT 3 A B C F1 F1 F2 F2...

Страница 4: ...very system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 16 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N TO IN D UNIT F1 F2 A1P A1P DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 1 2 6 3 3 4 5...

Страница 5: ...4 5 6 Heat pump system Heat recovery system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3...

Страница 6: ...sult in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive leak can lead to oxygen depletion especially in base ments and an asphyxiat...

Страница 7: ...on tribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrig erant piping installation Read the chapter Refrigerant Pip ing and follow...

Страница 8: ...itches off automatically in order to protect the unit from freezing Hold ambient temperature at 35 95 F Heat release from the unit 0 64 kW hour Model 72 84 It is therefore recommended to always ventil...

Страница 9: ...emale Thread 1 2FPS 2 female Thread General RWEYQ216PTJU RWEYQ252PTJU Nominal cooling capacity 2 MBh 216 252 Nominal cooling capacity 3 MBh 243 283 5 Nominal input cooling heating 4 kW 12 60 12 00 16...

Страница 10: ...ower without fail Open type tower cannot be used 4 Strainer Install the strainer accessory without fail at the inlet of water pip ing If sands wastes rust particles etc are mixed in the water cir cula...

Страница 11: ...manner 7 1 When designing the equipment 1 Install the strainer accessory at the water inlet side adjacent to the outside unit in order to prevent any foreign materials such as dust sand etc from ente...

Страница 12: ...within the standard 2 Clean the strainer 3 Make sure that the flow rate is correct 4 Make sure that the operational conditions pressure flow rate outlet temperature etc are normal 2 Because the plate...

Страница 13: ...fect but also may cause the capacitor to overheat due to high frequency waves Therefore never install a phase advancing capacitor Keep power imbalance within 2 of the supply rating 1 Large imbalance w...

Страница 14: ...electromagnetic switch for the water pump to each outside unit Select without fail an auxiliary a contact able to switch min imum load of DC15V 1mA When connecting for each outside unit Connect to the...

Страница 15: ...erminals for connections to the power terminal block When none is available follow the instructions below Do not connect wiring of different thicknesses to the power termi nal block Slack in the power...

Страница 16: ...s always required When installing the piping follow the instructions in the installation manual that comes with the kit Restriction for the installation of the outside unit multi connection piping kit...

Страница 17: ...cal piping with the provided insulation to prevent it from coming into contact with the casing Precautions for installation of units NOTE The outside unit multi connection piping kit that is sold sepa...

Страница 18: ...c d e f r s t g h j k l m n o p i 23 3 lbs Total length ft of liquid piping size at 7 8 0 235 lbs ft Total length ft of liquid piping size at 3 8 Total length ft of liquid piping size at 1 4 Total len...

Страница 19: ...etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be sure to...

Страница 20: ...refrigerant 9 10 Stop valve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without...

Страница 21: ...onfiguration on the main unit Any settings made on a sub unit will be ignored After this close the electrical compo nents box lid Always perform configuration after turning ON the power To learn the s...

Страница 22: ...rding to local regulations or standards The following standards may be applicable if local regulations are not available The VRV System like other air conditioning systems uses R410A as refrigerant R4...

Страница 23: ...e open ings above and below the door which are each equivalent in size to 0 15 or more of the floor area 3 Calculating the refrigerant density using the results of the calcula tions in steps 1 and 2 a...

Страница 24: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P153897 12P EM09A022 0910 FS...

Отзывы: