Control Specification
SiUS041111
36
Function and Control
3.3
Controls at Mode Changing / Start-up
3.3.1 Preheating Operation
Outline
The inverter operation in open phase starts with the conditions of the preheating command from the
indoor unit, the outdoor temperature, and the discharge pipe temperature.
Detail
09/12 class
Outdoor temperature
7°C (44.6°F)
Control A (preheating for normal state)
Outdoor temperature < 7°C (44.6°F)
Control B (preheating of increased capacity)
Control A
ON condition
Discharge pipe temperature < 10°C (50°F)
OFF condition
Discharge pipe temperature > 12°C (53.6°F)
Radiation fin temperature
90°C (194°F)
Control B
ON condition
Discharge pipe temperature < 20°C (68°F)
OFF condition
Discharge pipe temperature > 22°C (71.6°F)
Radiation fin temperature
90°C (194°F)
15/18/24 class
ON Condition
When the discharge pipe temperature is below 10°C (50°F), the inverter operation in open
phase starts.
OFF Condition
When the discharge pipe temperature is higher than 12°C (54°F), the inverter operation in open
phase stops.
3.3.2 Four-Way Valve Switching
Outline
In heating operation, current is conducted, and in cooling and defrosting, current is not conducted.
In order to eliminate the switching sound when the heating is stopped, as the four-way valve coil
switches from ON to OFF, the OFF delay switch of the four-way valve is carried out after the
operation stopped.
Detail
OFF delay switch of four-way valve:
The four-way valve coil is energized for 160 seconds after the operation is stopped.