Main Functions
SiUS041111
24
Function and Control
1.4
Fan Speed Control for Indoor Unit
Outline
Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H, and HH.
The airflow rate can be automatically controlled depending on the difference between the room thermistor
temperature and the target temperature. This is done through phase control and Hall IC control.
For more information about Hall IC, refer to the troubleshooting for fan motor on page 82.
Automatic Fan
Speed Control
In automatic fan speed operation, the step “SL” is not available.
= The airflow rate is automatically controlled within this range when the FAN setting button
is set to automatic.
<Cooling>
The following drawing explains the principle of fan speed control for cooling.
09/12 class
*In automatic fan speed operation, upper limit is at M tap in 30 minutes from the operation start.
15/18/24 class
<Heating>
On heating mode, the fan speed is regulated according to the indoor heat exchanger temperature
and the difference between the room thermistor temperature and the target temperature.
Note:
1. During POWERFUL operation, fan rotates at H tap + 80 ~ 90 rpm.
2. Fan stops during defrost operation.
Step
Cooling
Heating
09/12 class
15/18/24 class
LLL
LL
L
ML
M
MH
H
HH (POWERFUL)
(R11681)
(R6833)
(R6834)
(R14720)
Room thermistor temperature – target temperature
MH*
M
ML
L
+3˚C (+5.4˚F)
+2˚C (+3.6˚F)
+1˚C (+1.8˚F)
Fan speed
+2.5˚C (+4.5˚F)
+1.5˚C (+2.7˚F)
+0.5˚C (+0.9˚F)
Room thermistor temperature – target temperature
+1.5˚C (+2.7˚F)
+0.5˚C (+0.9˚F)
+2˚C (+3.6˚F)
+1˚C (+1.8˚F)
M
ML
L
Fan speed
(R14659)