SiUS39-602
Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting
213
Check No. 12
Check on pulse input of position signal of fan inverter PCB
(1) Disconnect the connector X2A while power supply OFF and operation OFF.
(2) Is the voltage between pins No. 4 and 5 on X2A approx. 15 V after power supply is turned on?
(3) Connect the connector X2A while power supply OFF and operation OFF.
(4) Check below conditions when the fan motor is rotated one turn manually under the condition
of operation OFF after power supply is turned ON.
Are the pulse (approx. 0 V and 5 V) generated 4 times between No. 1 and 5 on X2A?
Are the pulse (approx. 0 V and 5 V) generated 4 times between No. 2 and 5 on X2A?
Are the pulse (approx. 0 V and 5 V) generated 4 times between No. 3 and 5 on X2A?
Check No. 13
Power transistor check mode
When the inverter system malfunctions (malfunction of inverter, INV compressor), to locate
where the malfunction occurs, switching to the power transistor check mode of inverter in the
service mode setting enables not to judge the position detection signal malfunction but to output
waveform only during inverter operation. (The waveform can be checked by disconnecting the
wiring of compressor.)
After the completion of checks, return the system to the previous mode and wait for 30 seconds
or more until the discharge of capacitor is completed. Then, conduct a subsequent work.
Note:
Be sure to disconnect the compressor wiring when conducting the check operation mentioned above.
When the output voltage is approx. 100~200 V (10 Hz) and the voltage balance between
phases U-V, V-W, W-U is within ±5%, the inverter PCB is normal.
* Voltage output will be different depend on measuring device.
The condition (2) dose not appear
→
Faulty PCB
→
Replacing the PCB
The conditions (4) do not appear
→
Faulty hall IC
→
Replacing fan motor of outdoor unit
5 Gray
4 Pink
3 Orange
2 Blue
1 Yellow
GND
Vcc (approx. 15 V)
Position signal W
Position signal V
Position signal U
Содержание REYQ72
Страница 35: ...Specifications SiUS39 602 24 Specifications...
Страница 121: ...Field Setting SiUS39 602 110 Test Operation...
Страница 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Страница 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Страница 229: ...Piping Diagrams SiUS39 602 218 Appendix 1 Piping Diagrams 1 1 Outdoor Unit REYQ72M 96MTJU 4D045329A...
Страница 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Страница 234: ...SiUS39 602 Wiring Diagrams for Reference Appendix 223 2 2 Field Wiring REYQ72 96MTJU C 3D050361A...
Страница 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Страница 238: ...SiUS39 602 Wiring Diagrams for Reference Appendix 227 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116...
Страница 239: ...Wiring Diagrams for Reference SiUS39 602 228 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Страница 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Страница 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Страница 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...
Страница 269: ...SiUS39 602 iv Index...