SiUS39-602
Other Control
Function
67
5.3
Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using “Demand 1 Setting” or “Demand 2 Setting”.
To operate the unit with this mode, additional setting of “Continuous Demand Setting” or
external input by external control adapter is required.
[Demand 1 setting]
[Demand 2 setting]
★
Other protection control functions have precedence over the above operation.
5.4
Heating Operation Prohibition
Heating operation is prohibited above 24°C ambient temperature.
Setting
Standard for upper limit of power consumption
Demand 1 setting 1
Approx. 80%
Demand 1 setting 2 (factory setting)
Approx. 70%
Demand 1 setting 3
Approx. 60%
Setting
Standard for upper limit of power consumption
Demand 2 setting 2 (factory setting)
Approx. 40%
Содержание REYQ72
Страница 35: ...Specifications SiUS39 602 24 Specifications...
Страница 121: ...Field Setting SiUS39 602 110 Test Operation...
Страница 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Страница 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Страница 229: ...Piping Diagrams SiUS39 602 218 Appendix 1 Piping Diagrams 1 1 Outdoor Unit REYQ72M 96MTJU 4D045329A...
Страница 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Страница 234: ...SiUS39 602 Wiring Diagrams for Reference Appendix 223 2 2 Field Wiring REYQ72 96MTJU C 3D050361A...
Страница 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Страница 238: ...SiUS39 602 Wiring Diagrams for Reference Appendix 227 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116...
Страница 239: ...Wiring Diagrams for Reference SiUS39 602 228 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Страница 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Страница 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Страница 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...
Страница 269: ...SiUS39 602 iv Index...