SiUS39-602
Basic Control
Function
43
Compressor Operating Priority
INV:
Inverter compressor
STD1: Standard compressor 1
Each compressor operates in the following order of priority.
REYQ168M
INV
STD1
No. 1 No. 3
INV
STD1
No. 2 No. 4
No. 2 No. 4
No. 1 No. 3
REYQ144M
INV
STD1
No. 1 No. 3
INV
STD1
No. 2 No. 4
No. 2 No. 4
No. 1 No. 3
REYQ144M
STEP
Master unit INV
Slave unit INV
STD unit No.1
STD unit No.2
1
52Hz
OFF
OFF
OFF
2
57Hz
OFF
OFF
OFF
3
62Hz
OFF
OFF
OFF
4
68Hz
OFF
OFF
OFF
5
74Hz
OFF
OFF
OFF
6
81Hz
OFF
OFF
OFF
7
88Hz
OFF
OFF
OFF
8
96Hz
OFF
OFF
OFF
9
104Hz
OFF
OFF
OFF
10
110Hz
OFF
OFF
OFF
11
116Hz
OFF
OFF
OFF
12
124Hz
OFF
OFF
OFF
13
133Hz
OFF
OFF
OFF
14
143Hz
OFF
OFF
OFF
15
158Hz
OFF
OFF
OFF
16
165Hz
OFF
OFF
OFF
17
177Hz
OFF
OFF
OFF
18
189Hz
OFF
OFF
OFF
19
202Hz
OFF
OFF
OFF
20
210Hz
OFF
OFF
OFF
21
52Hz
189Hz
OFF
OFF
22
74Hz
189Hz
OFF
OFF
23
96Hz
189Hz
OFF
OFF
24
116Hz
189Hz
OFF
OFF
25
133Hz
189Hz
OFF
OFF
26
158Hz
189Hz
OFF
OFF
27
177Hz
189Hz
OFF
OFF
28
202Hz
189Hz
OFF
OFF
29
210Hz
189Hz
OFF
OFF
30
52Hz
189Hz
ON
OFF
31
88Hz
189Hz
ON
OFF
32
124Hz
189Hz
ON
OFF
33
158Hz
189Hz
ON
OFF
34
189Hz
189Hz
ON
OFF
35
210Hz
189Hz
ON
OFF
36
52Hz
189Hz
ON
ON
37
88Hz
189Hz
ON
ON
38
124Hz
189Hz
ON
ON
39
158Hz
189Hz
ON
ON
40
189Hz
189Hz
ON
ON
41
210Hz
189Hz
ON
ON
42
210Hz
210Hz
ON
ON
∗
•
Compressors are operated in the order of descending priorities.
•
Compressors may operate in a pattern other than those listed in above tables subject to the operating conditions.
•
“Master unit”, and “slave unit” in this section are the names for control, and they will be transferred according to the
priority of rotation system.
REYQ168M
STEP
Master unit INV
Slave unit INV
STD unit No.1
STD unit No.2
1
52Hz
OFF
OFF
OFF
2
57Hz
OFF
OFF
OFF
3
62Hz
OFF
OFF
OFF
4
68Hz
OFF
OFF
OFF
5
74Hz
OFF
OFF
OFF
6
81Hz
OFF
OFF
OFF
7
88Hz
OFF
OFF
OFF
8
96Hz
OFF
OFF
OFF
9
104Hz
OFF
OFF
OFF
10
110Hz
OFF
OFF
OFF
11
116Hz
OFF
OFF
OFF
12
124Hz
OFF
OFF
OFF
13
133Hz
OFF
OFF
OFF
14
143Hz
OFF
OFF
OFF
15
158Hz
OFF
OFF
OFF
16
165Hz
OFF
OFF
OFF
17
177Hz
OFF
OFF
OFF
18
189Hz
OFF
OFF
OFF
19
202Hz
OFF
OFF
OFF
20
210Hz
OFF
OFF
OFF
21
52Hz
189Hz
OFF
OFF
22
74Hz
189Hz
OFF
OFF
23
96Hz
189Hz
OFF
OFF
24
116Hz
189Hz
OFF
OFF
25
133Hz
189Hz
OFF
OFF
26
158Hz
189Hz
OFF
OFF
27
177Hz
189Hz
OFF
OFF
28
202Hz
189Hz
OFF
OFF
29
210Hz
189Hz
OFF
OFF
30
52Hz
189Hz
ON
OFF
31
88Hz
189Hz
ON
OFF
32
124Hz
189Hz
ON
OFF
33
158Hz
189Hz
ON
OFF
34
189Hz
189Hz
ON
OFF
35
210Hz
189Hz
ON
OFF
36
52Hz
189Hz
ON
ON
37
88Hz
189Hz
ON
ON
38
124Hz
189Hz
ON
ON
39
158Hz
189Hz
ON
ON
40
189Hz
189Hz
ON
ON
41
210Hz
189Hz
ON
ON
42
210Hz
210Hz
ON
ON
Содержание REYQ72
Страница 35: ...Specifications SiUS39 602 24 Specifications...
Страница 121: ...Field Setting SiUS39 602 110 Test Operation...
Страница 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Страница 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Страница 229: ...Piping Diagrams SiUS39 602 218 Appendix 1 Piping Diagrams 1 1 Outdoor Unit REYQ72M 96MTJU 4D045329A...
Страница 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Страница 234: ...SiUS39 602 Wiring Diagrams for Reference Appendix 223 2 2 Field Wiring REYQ72 96MTJU C 3D050361A...
Страница 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Страница 238: ...SiUS39 602 Wiring Diagrams for Reference Appendix 227 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116...
Страница 239: ...Wiring Diagrams for Reference SiUS39 602 228 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Страница 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Страница 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Страница 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...
Страница 269: ...SiUS39 602 iv Index...