3.3.2 Outdoor Unit
AH - 07 Damper rotation error [when
the self-cleaning decoration
panel is mounted]
The damper does not rotate
normally. Check for any
foreign matters around the
damper and for the operation
of the gear and limit switch.
AH - 08 Filter self-cleaning operation
error [when the self-cleaning
decoration panel is mounted]
The unit has not yet
completed the filter self-
cleaning operation even after
the lapse of specified period
of time. Check for any
external noise, etc.
C6 - 01 Faulty combination of indoor
unit PCB and fan PCB
A combination of indoor unit
PCB and fan PCB is
defective. Check whether the
capacity setting adaptor is
correct and the type of the fan
PCB is correct.
Error code
Troubleshooting
Description of error
Description of diagnosis
E7 - 01 Fan motor lock
The fan motor has caused
abnormal rotation. Check for
the connection of the
connector between the fan
motor and the outdoor unit
PCB. If the connection is
normal, replace the fan
motor. If this still cannot solve
the error, replace the outdoor
unit PCB.
L1 - 01
Instantaneous overcurrent
error (while in startup
operation)
Refer to the “L1” flow chart of
each manual and make a
diagnosis of the relevant unit
based on the Error code
shown to the left.
L1 - 02
Current sensor error in PCB
L1 - 03
Current offset error
L1 - 04
IGBT error
L1 - 05
Jumper setting error
L1 - 06
SP/MP-PAM overvoltage
error
Error code
Troubleshooting
Description of error
Description of diagnosis