Troubleshooting by Remote Controller
Si20-701_B
241
3.47
J1
Pressure Sensor
Abnormality
Remote Controller Display
J1
Applicable Models
RZQ-K, RZQ(S)-C, RZR-KU/HU
Method of Error Detection
The error is detected by the pressure measured with
pressure sensor
Error Decision Conditions
When the detect pressure becomes following;
• Detected pressure
≤
– 0.05MPa continues 185 sec.
• Detected pressure
≥
4.4MPa continues 185 sec.
Supposed Causes
Defective pressure sensor
Defective outdoor unit PCB
Incorrect connection of connector