Troubleshooting by Remote Controller
Si20-701_B
403
YES
YES
NO
NO
NO
Make the fuse
normal.
• In case of a fuse
can be
replaced,
replace the
fuse.
• In case of a fuse
cannot be
replaced,
replace PCB.
YES
YES
Replace the
outdoor unit
PCB.
Replace the
indoor unit PCB.
There is no
problem with the
unit. An external
factor (noise,
etc.) other than
unit failure may
be the cause.
Does the
fuse (F6U) have
continuity?
Error is
displayed again?
"
U4
" or "
UF
"
is displayed?
C
After turning OFF the
power supply, correctly
insert the connector of
the fan motor and then
restore the power.
B
YES
NO
Replace the
outdoor unit fan
motor.
Is
the resistance
value of the outdoor
unit fan motor
normal?
Check the resistance
value of the outdoor unit
fan motor.