Si20-701_B
Troubleshooting by Remote Controller
272
Note:
∗
1. Radiation fin temperature detection value
Model
Detection
Reset
RZQ
RZQ100~140B8W1B
76°C
66°C
RZR71KUV1
RZQ71B9V3B
RZQS71·100B7V3B
RZQ71C7V1B
RZQS71·100C7V1B
87°C
77°C
RZQG71LV1B
85°C
75°C
RZR100~140KUV1
RZR100~140HUY1
RZR-KUV2S
RZR-HUY2S
RZQ100~140C7V1B
RZQS125·140C7V1B
88°C
78°C
RZQG100~140LV1B
89°C
79°C
Is the error
displayed again
when the unit starts
operation?
YES
Replace the
outdoor unit
inverter PCB.
Continue the
operation.
NO
A
YES
Check the resistance
value of the thermistor
according to the
Troubleshooting "
P4
".
Is it
normally?
NO
Go to
troubleshooting
"
P4
".
A
B