
Si20-701_B
Troubleshooting by Remote Controller
396
Remote Controller Display
U4
Applicable Models
RZQ-C7
Method of Error Detection
Micro-computer checks if transmission between indoor
and outdoor units is normal.
Error Decision Conditions
When transmission is not carried out normally for a
certain amount of time
Supposed Causes
Wiring indoor-outdoor transmission wire is incorrect.
Outside cause (noise, etc.)
Defective indoor unit PCB
Defective outdoor unit PCB
Defective outdoor unit fan
Power supply -open phase etc.