AG 31-011 • REFRIGERANT PIPING DESIGN
shows a roof-mounted air-cooled chiller with a remote
evaporator inside the building.
1. There are two refrigeration circuits, each with a liquid
line supplying liquid refrigerant from the condenser to
a TX valve adjacent to the evaporator, and a suction
line returning refrigerant gas from the evaporator to the
suction connections of the compressor.
2.
There is a double suction riser on one of the circuits.
Double suction risers are covered inmore detail in the
Return in Suction and Discharge Risers” on page 21
Figure 3: Air-Cooled Chiller with Remote Evaporator
Remote
Evaporator
Air Cooled
Chiller with
Remote
Evaporator
Sight
Glass
TX
Valve
Solenoid
Valve
Filter-
Drier
Liquid
Line
Liquid
Line
Riser
Suction Line
Riser
Double
Suction
Line
Riser