AG 31-011 • REFRIGERANT PIPING DESIGN 50 www.DaikinApplied.com
Table 19: R-22 Refrigerant Charge
(Lbs . per 100 Feet of Pipe)
Line Size OD
Flow Area
Suction Line
Liquid Line
Discharge
Line
40°F
105°F
140°F
inches
in
2
1 .52 lb ./ft
3
68 .72 lb ./ft
3
6 .97 lb ./ft
3
1/2
0.145
0.15
6.92
0.70
5/8
0.233
0.25
11.12
1.13
7/8
0.484
0.51
23.10
2.34
1-1/8
0.825
0.87
39.37
3.99
1-3/8
1.257
1.33
59.99
6.08
1-5/8
1.779
1.88
84.90
8.61
2-1/8
3.905
4.13
186.36
18.90
2-5/8
4.772
5.04
227.73
23.09
3-1/8
6.812
7.20
325.08
32.97
3-5/8
9.213
9.74
439.66
44.58
4-1/8
11.977
12.66
571.57
57.96
5-1/8
18.665
19.72
890.74
90.33
6-1/8
26.832
28.35
1280.48
129.85
8-1/8
46.869
49.53
2236.69
226.81
Refrigerant weight per 100 feet of pipe is based on 105°F condensing
temperature and 10°F sub-cooling, 140°F discharge temperature, and 40°F
saturated suction temperature.
Table 20: R-134a Refrigerant Charge
(Lbs . per 100 feet of Pipe)
Line Size OD
Flow Area
Suction Line
Liquid Line
Discharge
Line
40°F
105°F
140°F
inches
in
2
1 .05 lb ./ft
3
69 .93 lb ./ft
3
5 .46 lb ./ft
3
1/2
0.145
0.11
7.04
0.55
5/8
0.233
0.17
11.32
0.88
7/8
0.484
0.35
23.50
1.83
1-1/8
0.825
0.60
40.06
3.13
1-3/8
1.257
0.92
61.04
4.76
1-5/8
1.779
1.30
86.39
6.74
2-1/8
3.905
2.85
189.64
14.79
2-5/8
4.772
3.48
231.74
18.08
3-1/8
6.812
4.96
330.81
25.81
3-5/8
9.213
6.71
447.41
34.90
4-1/8
11.977
8.73
581.63
45.38
5-1/8
18.665
13.60
906.42
70.71
6-1/8
26.832
19.56
1303.03
101.65
8-1/8
46.869
34.16
2276.08
177.57
Refrigerant weight per 100 feet of pipe is based on 105°F condensing
temperature and 10°F sub-cooling, 140°F discharge temperature, and 40°F
saturated suction temperature.
Table 21: R-410A Refrigerant Charge
(Lbs . per 100 feet of Pipe)
Line Size OD
Flow Area
Suction Line
Liquid Line
Discharge
Line
40°F
105°F
140°F
inches
in
2
2 .21 lb ./ft
3
58 .37 lb ./ft
3
12 .57 lb ./ft
3
1/2
0.145
0.22
5.88
1.27
5/8
0.233
0.36
9.44
2.03
7/8
0.484
0.74
19.62
4.22
1-1/8
0.825
1.26
33.44
7.20
1-3/8
1.257
1.93
50.95
10.97
1-5/8
1.779
2.72
72.11
15.53
2-1/8
3.905
5.98
158.29
34.09
2-5/8
4.772
7.31
193.43
41.66
3-1/8
6.812
10.43
276.12
59.46
3-5/8
9.213
14.11
373.45
80.42
4-1/8
11.977
18.34
485.48
104.55
5-1/8
18.665
28.59
756.58
162.93
6-1/8
26.832
41.10
1087.63
234.22
8-1/8
46.869
71.79
1899.82
409.12
Refrigerant weight per 100 feet of pipe is based on 105°F condensing
temperature and 10°F sub-cooling, 140°F discharge temperature, and 40°F
saturated suction temperature.
Table 22: R-407C Refrigerant Charge
(lbs . Per 100 Feet of Pipe)
Line Size OD
Flow Area
Suction Line
Liquid Line
Discharge
Line
40°F
105°F
140°F
inches
in
2
1 .69 lb ./ft
3
64 .65 lb ./ft
3
8 .64 lb ./ft
3
1/2
0.145
0.17
6.51
0.87
5/8
0.233
0.27
10.46
1.40
7/8
0.484
0.57
21.73
2.91
1-1/8
0.825
0.97
37.04
4.95
1-3/8
1.257
1.48
56.43
7.55
1-5/8
1.779
2.09
79.87
10.68
2-1/8
3.905
4.59
175.32
23.44
2-5/8
4.772
5.61
214.24
28.65
3-1/8
6.812
8.01
305.83
40.89
3-5/8
9.213
10.83
413.63
55.30
4-1/8
11.977
14.09
537.72
71.90
5-1/8
18.665
21.95
837.98
112.04
6-1/8
26.832
31.56
1204.65
161.07
8-1/8
46.869
55.12
2104.22
281.34
Refrigerant weight per 100 feet of pipe is based on 105°F condensing
temperature and 10°F sub-cooling, 140°F discharge temperature, and 40°F
saturated suction temperature.