www.DaikinApplied.com 49
AG 31-011 • REFRIGERANT PIPING DESIGN
Table 17: R-410A Minimum Capacity for Discharge Riser (Tons)
Saturated
Suction
Temp
Discharge
Temp
Pipe O .D . (inches)
(°F)
(°F)
1/2
5/8
3/4
7/8
1-1/8
1-3/8
1-5/8
2-1/8
2-5/8
3-1/8
3-5/8
4-1/8
Area (in
2
)
0 .146
0 .233
0 .348
0 .484
0 .83
1 .26
1 .78
3 .094
4 .770
6 .812
9 .213
11 .97
80
140
0.33
0.610
1.060
1.590
3.19
5.54
8.75
13.80
24.40
38.90
57.80
81.70
100
160
0.34
0.628
1.092
1.638
3.29
5.71
9.01
14.21
25.13
40.07
59.53
84.15
120
180
0.35
0.647
1.125
1.687
3.38
5.88
9.28
14.64
25.89
41.27
61.32
86.68
ASHRAE Handbook Refrigeration, Chapter 2, 2006.
© American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.,
Refrigeration capacity in tons based on saturated suction temperature of 40°F with 15°F superheat at indicated saturated
condensing temperature with 15°F sub-cooling. For other saturated suction temperatures with 15°F superheat, use correction
factors in the following table. (Table data based on line size pressure drop formula shown on page 2.17 of ASHRAE Handbook
Refrigeration 2006.)
Saturated Suction Temperature (°F)
0
20
40
60
0.90
0.94
1.00
1.06
Table 18: R-407C Minimum Capacity for Discharge Riser (Tons)
Saturated
Suction
Temp
Discharge
Temp
Pipe O .D . (inches)
(°F)
(°F)
1/2
5/8
3/4
7/8
1-1/8
1-3/8
1-5/8
2-1/8
2-5/8
3-1/8
3-5/8
4-1/8
Area (in
2
)
0 .146
0 .233
0 .348
0 .484
0 .83
1 .26
1 .78
3 .094
4 .770
6 .812
9 .213
11 .97
80
140
0.29
0.530
0.913
1.390
2.79
4.85
7.67
12.10
21.30
33.99
50.70
71.40
100
160
0.30
0.546
0.940
1.432
2.87
5.00
7.90
12.46
21.94
35.01
52.22
73.54
120
180
0.31
0.562
0.969
1.475
2.96
5.15
8.14
12.84
22.60
36.06
53.79
75.75
Refrigeration capacity in tons based on saturated suction temperature of 40°F with 30°F superheat at indicated saturated
condensing temperature with 10°F subcooling. For other saturated suction temperatures with 30°F superheat, use correction
factors in the following table. (Table data based on line size pressure drop formula shown on page 2.17 of ASHRAE Handbook
Refrigeration 2006.)
Saturated Suction Temperature (°F)
0
20
40
60
0.96
0.98
1.00
1.02