3
|
Components
Service manual
92
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
3
Manually rotate the fan and check the friction of the DC fan motor shaft
bearing.
Is the DC fan motor shaft friction
normal?
Action
Yes
Perform an electrical check of the DC
fan motor assembly, see
91].
No
Replace the DC fan motor assembly, see
To perform an electrical check of the DC fan motor assembly
Prerequisite:
First perform a mechanical check of the DC fan motor assembly, see
91].
1
Remove the cover from the switch box; see
151].
2
Disconnect the DC fan motor connector from the appropriate PCB.
3
Measure the resistance between the pins 1-2, 1-3, and 2-3 of the DC fan
motor connector.
Result:
All measurements MUST be approximately the same.
DC fan motor measurements are
correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Replace the DC fan motor, see
92].
Repair procedures
To remove the DC fan motor assembly
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
151].
1
Remove the switch box, see
2
Click the indoor unit fan motor cover out of the indoor unit. If needed, remove
the screw (if installed) on the right hand side of the fan motor cover for easier
removal.