Wall mounted indoor unit
a
Wifi control PCB assembly
a
A
A
Floor standing indoor unit
a
Wifi control PCB assembly
Is the measured power supply voltage
correct?
Action
Yes
Skip the next step..
No
Continue with the next step.
4
Measure the output voltage between between the pins 4‑5 on the connector
S801 on the indoor unit main PCB.
Result:
The measured voltage MUST be 10~16 V DC.
Is the output voltage on the indoor unit
main PCB correct?
Action
Yes
Replace the wifi control PCB wiring
harness, see
No
Perform a check of the indoor unit main
PCB, see
5
As there are no further check procedures for this component, perform a check
of the indoor unit main PCB to check if the wifi control PCB needs to be
replaced. See
102].