3
|
Components
Service manual
84
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
INFORMATION
The expansion valve and motor can have a different configuration / layout.
5
Reinstall the putty.
a
b
c
A
a
a
a
A
Class 20~35 unit
a
Putty
b
Expansion valve pipe
c
Expansion valve body
a
b
c
A
A
Class 42~71 unit
a
Putty
b
Expansion valve pipe
c
Expansion valve body
6
Reinstall the putty.
7
To install the expansion valve motor, see
79].
8
Add refrigerant to the refrigerant circuit, see
209].
To install the expansion valve motor with clip
1
Install the expansion valve motor on the expansion valve body.
INFORMATION
The expansion valve motor is equipped with a pipe retention clip. Install the pipe
retention clip over the pipe to lock the expansion valve motor.