ESIE19-06
|
Part 2. Troubleshooting
2.2. Error based troubleshooting
21/01/20
|
Version 1.1
Page 21
Modular L Smart
A6
17
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Exhaust air FAN
②
(address 4)
hall-sensor location detection
error
A6
22
on
off
flashing
keep running
fan power measurement retry
Alarm
A8
01
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
power supply error
AJ
01
flashing
flashing
flashing
error
①
(reset remote control)
stop operation
capacity adaptor setting error
C0
01
flashing
flashing
flashing
generic error
C1
01
flashing
flashing
flashing
error
②
(recover automati-
cally)
stop operation
error (between control & inv PCB)
C6
01
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Supply air FAN
①
(address 1)
driver combination mismatch
C6
02
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Supply air FAN
①
(address 1)
driver setting mismatch
C6
05
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Supply air FAN
①
(address 1)
EEPROM read abnormality
C6
06
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Supply air FAN
①
(address 1)
thermistor malfunction abnormal-
ity
C6
07
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Supply air FAN
①
(address 1) fin
temperature abnormality
C6
11
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Exhaust air FAN
①
(address 3)
driver combination mismatch
C6
12
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Exhaust air FAN
①
(address 3)
driver setting mismatch
C6
15
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Exhaust air FAN
①
(address 3)
EEPROM read abnormality
C6
16
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Exhaust air FAN
①
(address 3)
thermistor fault abnormality
C6
17
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Exhaust air FAN
①
(address 3)
fin temperature abnormality
C6
21
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Supply air FAN
②
(address 2)
driver combination mismatch
C6
22
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Supply air FAN
②
(address 2)
driver setting mismatch
C6
25
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Supply air FAN
②
(address 2)
EEPROM read abnormality
C6
26
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Supply air FAN
②
(address 2)
thermistor malfunction abnormal-
ity
C6
27
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Supply air FAN
②
(address 2) fin
temperature abnormality
C6
31
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Exhaust air FAN
②
(address 4)
driver combination mismatch
C6
32
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Exhaust air FAN
②
(address 4)
driver setting mismatch
Error code
Unit
No.
Error level
Operation state
Cause of error
Main
Sub
Содержание Modular L Smart
Страница 1: ...Service Manual Modular L Smart ESIE19 06 ...
Страница 6: ...ESIE19 06 Page 6 21 01 20 Version 1 1 Modular L Smart ...
Страница 16: ...ESIE19 06 Part 1 Introduction 1 4 How to use Page 16 21 01 20 Version 1 1 Modular L Smart ...
Страница 59: ...ESIE19 06 Part 4 Maintenance 4 1 HRV unit 21 01 20 Version 1 1 Page 59 Modular L Smart ...
Страница 60: ...ESIE19 06 Part 4 Maintenance 4 1 HRV unit Page 60 21 01 20 Version 1 1 Modular L Smart ...
Страница 62: ...ESIE19 06 Part 5 Appendix Page 62 21 01 20 Version 1 1 Modular L Smart This page is deliberately left blank ...
Страница 86: ...ESIE19 06 Part 5 Appendix 5 4 Switch box Modular L Smart Page 86 21 01 20 Version 1 1 Figure 5 23 Control PCB ...