ESIE19-06
|
Part 2. Troubleshooting
2.2. Error based troubleshooting
Page 22
21/01/20
|
Version 1.1
Modular L Smart
C6
35
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Exhaust air FAN
②
(address 4)
EEPROM read abnormality
C6
36
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Exhaust air FAN
②
(address 4)
thermistor fault abnormality
C6
37
flashing
flashing
flashing
error
①
(reset remote control)
stop fan operation
(cause of fault)
Exhaust air FAN
②
(address 4)
fin temperature abnormality
CH
-
on
off
off
warning
keep running
CO
2
sensor warning
CJ
-
on
off
off
warning
keep running
thermistor fault "BRC..."
user interface
60
-
flashing
flashing
flashing
error
②
(recover automati-
cally)
stop operation
external error input
60
-
on
off
flashing
alert
keep running
external error input
64
01
on
off
flashing
alert
keep running
air return thermistor alert
64
02
on
off
flashing
alert
keep running
out of operation range alarm due
to air return thermistor
65
01
on
off
flashing
alert
keep running
outdoor air intake thermistor alert
65
02
on
off
flashing
alert
keep running
out of operation range alarm due
to outdoor air thermistor
65
03
flashing
flashing
flashing
error
①
(reset remote control)
stop operation
low outdoor temperature opera-
tion alarm during filter contamina-
tion function (field setting
29-0-04/05)
6A
-
on
off
flashing
alert
keep running
damper alert
6A
-
flashing
flashing
flashing
error
②
(recover automati-
cally)
stop operation
damper error
U5
-
flashing
flashing
flashing
error
②
(recover automati-
cally)
stop operation
user interface transmission error
missing
U5
-
flashing
flashing
flashing
error
②
(recover automati-
cally)
stop operation
user interface control communica-
tion error
U8
-
flashing
flashing
off
error
②
(recover automati-
cally)
stop operation
transmission abnormality between
main/slave liquid crystal remote
control
UA
-
flashing
flashing
off
error
②
(recover automati-
cally)
stop operation
remote control combination failure
UC
-
on
off
off
warning
keep running
duplication of central group
address warning
UE
-
flashing
flashing
flashing
error
②
(recover automati-
cally)
stop operation
central control communication
error
UE
-
on
off
flashing
alert
keep running
central control transmission alert
Error code
Unit
No.
Error level
Operation state
Cause of error
Main
Sub
Содержание Modular L Smart
Страница 1: ...Service Manual Modular L Smart ESIE19 06 ...
Страница 6: ...ESIE19 06 Page 6 21 01 20 Version 1 1 Modular L Smart ...
Страница 16: ...ESIE19 06 Part 1 Introduction 1 4 How to use Page 16 21 01 20 Version 1 1 Modular L Smart ...
Страница 59: ...ESIE19 06 Part 4 Maintenance 4 1 HRV unit 21 01 20 Version 1 1 Page 59 Modular L Smart ...
Страница 60: ...ESIE19 06 Part 4 Maintenance 4 1 HRV unit Page 60 21 01 20 Version 1 1 Modular L Smart ...
Страница 62: ...ESIE19 06 Part 5 Appendix Page 62 21 01 20 Version 1 1 Modular L Smart This page is deliberately left blank ...
Страница 86: ...ESIE19 06 Part 5 Appendix 5 4 Switch box Modular L Smart Page 86 21 01 20 Version 1 1 Figure 5 23 Control PCB ...