www.DaikinApplied.com 39
IOM 1210-7 • MAGNITUDE
®
MODEL WMC CHILLERS
o
peraTIon
Bypass VALVE Setpoints
Figure 34: Bypass VALVE Setpoint Screen
Table 13: Bypass VALVE Setpoint Settings
Description
Default
Range
Password
Comments
Temp - Max Start Position [SP11]
90 °F
0 to 100 °F
T
Condenser EWT at which valve should be open to tower. Valve position is set to SP10
EXV Valve Start Position
Closed
Open-Closed
T
Select valve position to either open or closed.
Release at LR
1.00
1-5
T
Lift Ratio at which the EXV start pos is released for normal control
Unload Target LR
2.2
1-5
T
Target to which the chiller will unload to stage on another comp.
It could be a Lift Ratio or a Lift pressure.
Stage Lift Type
Ratio
Ratio-
Pressure
T
Select either Ratio or Pressure as lift type
Stage EXV Control
Auto
0-100%
T
Hold at selected percentage
EXV Duration
0 sec
0-60 sec
T
Time the EXV position is held during staging event.
Start Ready + Next-On
1
0-1
T
Configures the Ready-To-Start indicator, 1 = Chiller as a compressor ready to start
next. 0 = Chiller as a compressor available to start (it may not be next compressor
starting).
EXV Gain
78
Configurable
T
Gain selection based on chiller size and valve type. Alternate Mode – Gain based on
chiller function (Cool/Ice/Heat).
EXV Offset
700
Configurable
T
Offset selection based on chiller size and valve type. Alternate Mode – Offset based on
chiller function.
SH Dropout Temp
10°F
10-50
T
Selected temperature that the EXV transitions from Pull-down control, to running on
condition.
NOTE:
relies on Setpoints 1 and 2 in
. The setpoints listed in
should only be changed
by a Daikin Applied technician. Contact a Daikin Applied service representative for more information.
Содержание Magnitude
Страница 4: ......
Страница 23: ...Installation www DaikinApplied com 21 IOM 1210 7 MAGNITUDE MODEL WMC CHILLERS...
Страница 24: ...IOM 1210 7 MAGNITUDE MODEL WMC CHILLERS 22 www DaikinApplied com Installation Figure 20 Wiring Index...
Страница 25: ...Installation www DaikinApplied com 23 IOM 1210 7 MAGNITUDE MODEL WMC CHILLERS...
Страница 26: ...IOM 1210 7 MAGNITUDE MODEL WMC CHILLERS 24 www DaikinApplied com Installation Figure 21 Controller Box Wiring...