15
|
About the app
Installer and user reference guide
119
BK+S
Madoka wired remote controller
4P596268-1A – 2022.02
Field settings type
Procedure
Remote controller
▪
Set the field setting type to "Remote
controller".
▪
Define a mode.
▪
Define the setting by tapping the right
tile in the app. In the field settings
table, find settings in the SW column.
▪
Define a value for that setting.
Default values
Field setting default values are different depending on the indoor unit model. For
more information, see the service manual of the indoor units. For the following
field settings, the default values are the same for all indoor unit models:
Field setting
Default value
Thermostat sensor
02
Setback
04
Window contact B1
02
Key card contact B2
02
Airflow direction range
02
Remote controller thermostat sensor
02
Rotation overlap time
03
INFORMATION
▪
The connection of optional accessories to the indoor unit might cause changes to
some field settings. For more information, see the installation manual of the
optional accessory.
▪
For details about the specific field settings of each type of indoor unit, see the
installation manual of the indoor units.
▪
Outdoor unit field settings can only be configured via the outdoor unit PCB. For
more information, see the installation manual of the outdoor unit.
▪
Field settings that are not available for a connected indoor unit are not displayed.
Duty rotation
Activate Duty rotation to let the indoor units operate alternately (one indoor unit
alternately inactive), this to increase system lifespan and reliability.
Duty rotation is designed for units operating in critical applications (e.g. in server
rooms that require lots of cooling). In these cases, the system is equipped with an
extra backup unit. Activating Duty rotation then allows for:
▪
Rotation
: because the system is equipped with more units than are required to
provide the heating/cooling load, one of the units can remain inactive during
normal operation. After a set time (i.e. "Rotation cycle time"), the inactive unit
will start operation, and a previously active unit will become inactive (i.e. duty
rotation). Because the units only operate alternately, the lifespan of the system
increases.
▪
Backup
: having a backup unit allows for system redundancy. If an active unit goes
into error, Duty rotation makes sure an inactive one takes over.
Содержание Madoka BRC1H82K