5
|
Operation
Installer and user reference guide
21
BK+S
Madoka wired remote controller
4P596268-1A – 2022.02
Auto
INFORMATION
In case of indoor unit setpoint logic, the system cannot run in Auto operation mode.
Therefore, to allow for Auto operation mode, go for remote controller setpoint logic.
For more information, see the Madoka Assistant app and
The Auto operation mode logic depends on the set setpoint logic (Madoka
Assistant app setting).
Single setpoint
Dual setpoint
0.5°C ~
2°C
0.5°C ~
2°C
0.5°C ~
2°C
0.5°C ~
2°C
C2
+ C1
SP
+ C1
C2
0.5°C ~
2°C
0.5°C ~
2°C
0.5°C ~
2°C
0.5°C ~
2°C
DIFF
C2
+ C1
SP
+ C1
C2
SP
Cooling setpoint
Heating setpoint
DIFF
Minimum setpoint differential between the Heating and the Cooling setpoint
+C1
Changeover setpoint (with guard timer)
C2
Forced changeover setpoint
0.5°C~2°C
Field settable temperature intervals between setpoints
INFORMATION
The default value of the settable temperature range (0.5°C~2°C) is 0.5°C.
A changeover from the one operation mode to the other occurs in the following
cases:
Case 1: primary changeover ( +C1)
A changeover occurs from the moment the room temperature rises above/drops
below the Cooling/Heating changeover setpoint (C1), and the guard timer has run
out.
Example: