3-60
3.10.3.2 H-code
=The alarm is displayed when the control temperature does not decrease by 3˚C or more
every 4 hours during pull-down operation.
H001
=The alarm is displayed when the total time out of "in-range" reaches 2 hours. (Counting is
not performed during defrosting).
H002
=The alarm will be displayed when the total time below setpoint –1˚C reaches 2 hours.
=The alarm will be displayed when the total time below setpoint –2˚C reaches 2 hours.
H004
H003
t
4Hr
SP+1˚C
SP
If "t" is smaller than 3˚C, code "H001" appears.
※
This criteria (3˚C) can be adjusted from 1, 2, 5 or 10˚C.
Inside
Temperature
time
t
1
> 2Hrs
H002
SP+1
SP
t
2
t
3
t
1
+t
2
+t
3
> 2Hrs
H003
> 2Hrs
H004
SP–1
SP
SP–2
t
1'
t
1
t
2
t
2'
t
1
+t
2
t
1
'+t
2
'
Figure2
Figure3
Figure4
https://daikin-p.ru