6-8
Location
Socket No.
Malfunction or Alarm
when the socket is disconnected or loosened.
Applicable to
LXE10D
SMV Board
(EC6)
CN81
(White)
No Alarm······No power supply to Controller
-----
CN82 (Red)
No Alarm······No power supply to Controller
-----
CN83
(Yellow)
F803
-----
CN84 (Blue)
F603
-----
PT/CT
Board (EC6)
CN1
F705
Yes
CPU Board
(CN1)
CN15
No Alarm······No communication to cpomputor for data down loading
Yes
Terminal
Board
(TB1)
CN2
F101
Yes
Terminal
Board
(TB1)
CN6
F803, E401, E403, E409, E411, E413, E415
("E" displayed in SS, RS temperature indication for E401, E403)
Yes
Fu5
No Alarm······No power supply to Controller
Yes
Terminal
Board
(TB1)
Fu4
F603, E315, E417, E421, E423
Yes
F705 E315 E417 E421 E423
No Alarm······No power supply to recorder
No Alarm······No power supply to Controller
Yes
Yes
Yes
Yes
Yes
Yes
Applicable to
LXE10D
-----
Malfunction and Alarm
when the socket is disconnected or loosened.
LXE10E
CN2
Yes
I/O Board
(EC2)
CN26
Yes
CN13
Yes
CN16
No Alarm······No power supply to MODEM
CN18
No Alarm······No "signal" power supply to EV
CN1
E109
→
F109 (F803)
CN3
No Alarm······No power to PCC (No operation)
CN4
No Alarm······No power supply to Controller
CN7
F406 E407 E402 E404
("E" displayed in DRS, DSS, EIS, SGS temperature indication)
Location
Fuse No.
Malfunction or Alarm
when the fuse is broken.
Fu6
No Alarm······No power supply to Monitoring Cirit
Fu1
F101
Yes
Fu2
BSV
-----
Fu3
E109
→
F109 (F803)······No power to LSV (LSV close)
Yes