
2-14
2.5 OPERATION MODES AND CONTROL
There are two main types of operation modes: the cargo cooling control mode and the unit
inspection mode.
The cargo cooling control mode is explained in this section.
※
For the unit inspection mode, refer to section 3.9.
The relationship between the operation mode and setting temperature is as follows.
※
For details, refer to section 2.5.1 to 2.5.4
Operation mode
Setting temperature
Control sensor
Operation description
Frozen mode
–10.1˚C to –30.0˚C
Return air
Compressor ON/OFF control
(+13.8˚F to –22.0˚F)
temperature sensor
Partial frozen
–3.0˚C to –10.0˚C
Return air
Capacity control operation
mode
(+26.6˚F to +14˚F)
temperature sensor
with suction modulating valve
and hot-gas bypass control
+25.0˚C to –2.9˚C
Supply air
Capacity control operation
Chilled mode
(+77˚F to +26.8˚F)
temperature sensor
with suction modulating valve
and hot-gas bypass control
Defrosting mode
–
–
Hot-gas defrosting with
refrigerant metering control
https://daikin-p.ru