89
3.2.6 List of Detailed Error Codes (SkyAir)
Indoor unit
Error code
Troubleshooting
Description of error
Description of diagnosis
A6 - 01
Fan motor locked
A locked fan motor current has been detected.
Turn the fan by hand to check for the connection of
connectors.
A6 - 10
Fan overcurrent error
A fan motor overcurrent has been detected.
Check for the connection of the connector between the fan
motor and the PC board for the fan. If the connection is
normal, replace the fan motor. If this still cannot solve the
error, replace the PC board for the fan.
A6 - 11
Fan position detection error
An error in the detection of position of the fan motor. Check for
the connection of the connector between the fan motor and
the PC board for the fan. If the connection is normal, replace
the fan motor. If this still cannot solve the error, replace the PC
board for the fan.
AH - 03
Transmission error (between the self-cleaning
decoration panel and the indoor unit)
[when the self-cleaning decoration panel is
mounted]
Check for the connection of the harness connector between
the panel PC board and the indoor unit PC board.
AH - 04
Dust detection sensor error
[when the self-cleaning decoration panel is
mounted]
Check for the connections of the connector X12A on the panel
PC board and the connectors X18A and X19A on the sensor
PC board.
AH - 05
Dust collection sign error
[when the self-cleaning decoration panel is
mounted]
Check for clogging with dust at the dust collection port as well
as in the brush unit, S-shaped pipe, and dust box.
Furthermore, check for any stains of the light, receiving and
emitting parts of the infrared unit.
AH - 06
Air filter rotation error
[when the self-cleaning decoration panel is
mounted]
Check for anything getting in the way of rotating the filter (e.g.
the filter comes off or the drive gear is clogged with foreign
matters).
AH - 07
Damper rotation error
[when the self-cleaning decoration panel is
mounted]
The damper does not rotate normally. Check for any foreign
matters around the damper and for the operation of the gear
and limit switch.
AH - 08
Filter self-cleaning operation error
[when the self-cleaning decoration panel is
mounted]
The unit has not yet completed the filter self-cleaning
operation even after the lapse of specified period of time.
Check for any external noise, etc.
C6 - 01
Faulty combination of indoor unit PC board and
fan PC board
A combination of indoor unit PC board and fan PC board is
faulty. Check whether the capacity setting adapter is correct
and the type of the fan PC board is correct.
Содержание GQI-Eco Series
Страница 2: ......
Страница 6: ...ESIE15 13B iv Table of Contents...
Страница 14: ...Introduction ESIE15 13B xii...
Страница 18: ...Outlook Outdoor Units ESIE15 13B 4 General Information 2 Outlook Outdoor Units...
Страница 22: ...Operating range ESIE15 13B 8 General Information...
Страница 108: ...Emergency Operation ESIE15 13B 94 Field Setting...