Troubleshooting by Remote Controller
Service Diagnosis
169
4.32 Refrigerant Shortage (Error)
Remote
Controller
Display
U0
Applicable
Models
RZQG
Method of Error
Detection
(In cooling)
Detection based on difference in temperature between temperature set by remote controller and
indoor suction air temperature, electronic expansion valve opening degree, compressor
frequency and low pressure.
(In heating)
Detection based on difference in temperature between temperature set by remote controller and
indoor suction air temperature, electronic expansion valve opening degree during the control of
suction air superheating, high pressure, indoor heat exchanger temperature and indoor suction
air temperature.
Error Decision
Conditions
(In cooling)
When compressor frequency does not increase even though the load is heavy because the
electronic expansion valve is opened to the fullest extent
(In heating)
When suction gas superheat degree is large, compressor frequency is low and the electronic
expansion valve is opened to the fullest extent even though heating load is heavy
[If high pressure is lower than saturated pressure for indoor heat exchanger temperature (or
indoor suction air temperature), error is confirmed.]
Supposed
Causes
Refrigerant shortage
Clogged refrigerant piping system
Mismatching of wiring and piping
Stop valve is not opened
Содержание GQI-Eco Series
Страница 2: ......
Страница 6: ...ESIE15 13B iv Table of Contents...
Страница 14: ...Introduction ESIE15 13B xii...
Страница 18: ...Outlook Outdoor Units ESIE15 13B 4 General Information 2 Outlook Outdoor Units...
Страница 22: ...Operating range ESIE15 13B 8 General Information...
Страница 108: ...Emergency Operation ESIE15 13B 94 Field Setting...