ESIE15-13B
Function Details
Function and Control
53
Cooling
Field setting to control the different value:
Heating
Field setting to control the different value:
Note:
If quick cooling/heating function is selected by the customer via remote controller, the unit will
go into quick cooling/heating for 20 minutes, neglecting the selected Te/Tc. After 20 minutes,
the selected Te/Tc setting will receive priority again.
Example:
The customer has to make a choice:
Fix the Te Lower limit and/or the Tc upper limit on a certain value.
OR
Choose the weather dependent Te Lower limit or Tc Upper limit. In this case the customer can
select 2 different outdoor temperatures that will trigger the changeover to a different Te Lower
limit and/or Tc Upper limit.
B
A
Ta
C
D
TeS Lower Limit Value
Value
Setting
1
2
3
4
A
2-54-
9
11
13
15
B
2-57-
2
4
6
8
C
2-58-
14
17
20
23
D
2-59-
23
27
31
35
F
E
Ta
G
H
TcS Upper Limit Value
Value
Setting
1
2
3
4
E
2-60-
47
48
49
50
F
2-61-
43
44
45
46
G
2-62-
2
5
8
11
H
2-63-
15
18
21
24