ESIE15-13B
Field Setting from Remote Controller
Field Setting
65
Level
Setting Code Function
Setting
Description
Info
Re
mo
te
con
tro
ller
BRC1E
Remote controller setting (BRC1E)
1e
1
Unit of temperature
01
°C
02
Optional choice of °C or °F
in "Extended functions"
menu option
1x RETURN -> Extended
functions -> Unit of
temperature
2
"Away from Home
function"
After being activated
below/above the
temperature set in the main
menu (see setting 1b-a),
the "Away from Home
function" switches on the
interior unit and the system
runs without setpoint until
the temperature is once
again within the safe
range. (Heating 5°C - 10°C
/cooling 35°C - 40°C)
Only for master units in the
system (if necessary,
consider setting 22-9)
01
Not available
To activate the Away from
Home function, press right
arrow for 5 seconds.
In the display you will see
To deactivate, press right
arrow again for 5 seconds.
02
Available for heating mode
03
Available for cooling mode
04
Available for heating and
cooling mode
4
Weekly timer
01
Weekly timer is not
available
If the sequence timer is
also deactivated under 1e-
6, the "Timer settings"
menu option disappears
02
Weekly timer is available
1x RETURN -> Timer
adjustment -> Weekly timer
5
Clock display options
01
24-hour display
02
You can choose between
24-hour or 12-hour display
in the "Extended functions"
menu option
1x RETURN -> Extended
functions -> Time display
6
Sequence timer
01
Sequence timer is not
available
If the weekly timer is also
deactivated under 1e-4,
the "Timer settings" menu
option disappears
02
Sequence timer is
available
1x RETURN -> Timer
adjustment -> Sequence
timer
a
Sensor calibration of
remote controller sensor in
the master remote
controller
01
-3 K
As from BRC1E software
ver.04.00.03
02
-2.5 K
03
-2 K
04
-1.5 K
05
-1 K
06
-0.5 K
07
±0 K
08
+0.5 K
09
+1 K
b
Sensor calibration of
remote controller sensor in
the slave remote controller
01
-3 K
As from BRC1E software
ver.04.00.03
02
-2.5 K
03
-2 K
04
-1.5 K
05
-1 K
06
-0.5 K
07
±0 K
08
+0.5 K
09
+1 K
Содержание GQI-Eco Series
Страница 2: ......
Страница 6: ...ESIE15 13B iv Table of Contents...
Страница 14: ...Introduction ESIE15 13B xii...
Страница 18: ...Outlook Outdoor Units ESIE15 13B 4 General Information 2 Outlook Outdoor Units...
Страница 22: ...Operating range ESIE15 13B 8 General Information...
Страница 108: ...Emergency Operation ESIE15 13B 94 Field Setting...