FC66006893
59
3 way valve kit
FCU Models
Sizes
3 way valve
kit 230V on/
off 2 pipes
3 way valve
kit 230V on/
off 4 pipes
3 way valve
kit 230V on/
off 2 pipes
(simplified)
3 way valve kit
230V on/off 4
pipes (simplified)
3 way valve kit
24V on/off 2
pipes
3 way valve kit
24V on/off 4
pipes
3 way valve kit
24V proportional
2 pipes
3 way valve
kit 24V
proportional 4
pipes
Body
Watts STD
Coil (*)
Body Watts
ADD Coil - 4
Pipes (**)
Actuator
Watts 230V
on/off
Actuator Watts
24V on/off
Actuator
Watts 24V
proportional
FWZ - FWR
- FWS
02- 03
E2MV03B6 E4MV03B6 E2MVD03A6
E4MVD03A6
E2M2V03A6
E4M2V03A6
E2MPV03A6
E4MPV03A6 413112
413112
22CX230NC2 22CX24NC2-2 EMUJC-010
06
E2MV06B6 E4MV06B6 E2MVD06A6
E4MVD06A6
E2M2V06A6
E4M2V06A6
E2MPV06A6
E4MPV06A6
413134
413112
22CX230NC2 22CX24NC2-2 EMUJC-010
08
E2MV10B6 E4MV10B6
E2MVD10A6
E4MVD10A6
E2M2V10A6
E4M2V10A6
E2MPV10A6
E4MPV10A6
413134
413112
22CX230NC2 22CX24NC2-2 EMUJC-010
(*)Available for STD coil in 2 and 4 pipes kit.
(**)Available only for 3-way valve kits in 4 pipes units.
2 way valve kit
FCU Models
Sizes
2 way valve kit
230V on/off single
heat exchangers
2 way valve kit
230V on/off
additional heat
exchangers
2 way valve kit
24V on/off single
heat exchangers
2 way valve kit 24V
on/off additional
heat exchangers
2 way valve kit
24V proportional
single heat
exchangers
2 way valve kit
24V proportional
additional heat
exchangers
Body Watts single
heat exchangers
Body Watts
additional heat
exchangers
Actuator
Watts 230V
on/off
Actuator Watts
24V on/off
Actuator Watts 24V
proportional
FWZ - FWR - FWS
02 - 03 - 06
E2MV2B07A6
E2MV2B07A6
E2M2V207A6
E2M2V207A6
E2MPV207A6
E2MPV207A6
213112
213112
22CX230NC2
22CX24NC2-2
EMUJC-010
08
E2MV2B10A6
E2MV2B07A6
E2M2V210A6
E2M2V207A6
E2MPV210A6
E2MPV207A6
213134
213112
22CX230NC2
22CX24NC2-2
EMUJC-010
Hydraulic characteristics
Valve Part Number
DN
DN (mm)
Max working pressure PN (Bar)
Kvs
Kvs_bypass
ΔPs maximum static differential pressure at the ends of the
valve against which the valve can open [bar]
213112
1/2"M
15
16
1,7
-
2,5
213134
3/4"M
20
16
2,8
-
1,5
413112(*)
1/2"M
15
16
1,7
1,2
2
413134(*)
3/4"M
20
16
2,5
1,6
1
NOTE (*): 3 way 4 ports valves are the standard ones, NC, used only in mixing mode
FCU KIT VALVE
2 way pressure indipendent valve kit
Code
Description
Unit
PICV Valve (std. coil)
ON/OFF Actuator
(std. coil)
PICV Valve (add.
coil)
ON/OFF Actuator
(add. coil)
FWZSVPIC2V15
Valve kit PIC 3/4’’, ON-OFF 230V actuator, 2 pipes system
FWZ-R-S 2
AB-QM 15 4.0
TWA-Q 230V
\
\
FWZSVPIC2V20
Valve kit PIC 1’’, ON-OFF 230V actuator, 2 pipes system
FWZ-R-S 3-6
AB-QM 20 4.0
TWA-Q 230V
\
\
FWZSVPIC2V25
Valve kit PIC 1’’1/4, ON-OFF 230V actuator, 2 pipes system
FWZ-R-S 8
AB-QM 25
ABN-A5
\
\
FWZSVPIC2V1515
Valve kit PIC 3/4’’, ON-OFF 230V actuator, 4 pipes system (2 valves and
own kits) (with additional heat exchanger)
FWZ-R-S 2
AB-QM 15 4.0
TWA-Q 230V
AB-QM 15LF
TWA-Q 230V
FWZSVPIC2V2015
Valve kit PIC 1’’ and 3/4’’ ON-OFF 230V actuator, 4 pipes system (2
valves and own kits) (with additional heat exchanger)
FWZ-R-S 3-6
AB-QM 20 4.0
TWA-Q 230V
AB-QM 15 4.0
TWA-Q 230V
FWZSVPIC2V2520
Valve kit PIC 1’’1/4 and 1’’, ON-OFF 230V actuator, 4 pipes system (2
valves and own kits) (with additional heat exchanger)
FWZ-R-S 8
AB-QM 25
ABN-A5
AB-QM 20 4.0
TWA-Q 230V
Содержание FWZ
Страница 2: ......
Страница 61: ...FC66006893 61 12 3 FWEC10 3 pipes systems...
Страница 62: ...FWZ FWR FWS 62 12 4 FWEC3 FWZ R S 02 08...
Страница 63: ...FC66006893 63 12 5 FWEC3 FWZ R S 02 08 heating element...
Страница 64: ...FWZ FWR FWS 64 12 6 FWECSAPA FWZ R S 02 08 ON OFF valve...
Страница 65: ...FC66006893 65 12 7 FWECSAPA FWZ R S 02 08 ON OFF valve heating element...
Страница 66: ...FWZ FWR FWS 66 12 8 FWECSAPA FWZ R S 02 08 modulating valve...
Страница 67: ...FC66006893 67 12 9 FWECSAPA FWZ R S 02 08 modulating valve heating element...
Страница 68: ...Zandvoordestraat 300 B 8400 Oostende Belgium...