Outdoor Unit: RXS15/18LVJU
SiUS091133
325
Removal Procedure
5
Heat up the brazed part
of the discharge side
and disconnect it.
Cautions for restoration
1. Restore the piping by non-
oxidation brazing.
2. It is required to prevent the
carbonization of the oil inside
the four-way valve and the
deterioration of the gaskets
affected by heat. Keep below
120°C (248°F). Wrap the four-
way valve with a wet cloth and
provide water so that the cloth
does not dry.
In case of difficulty with gas
brazing machine
1. Disconnect the brazed part
where is easy to disconnect and
restore.
2. Cut pipes on the main unit with
a tube cutter in order to make it
easy to disconnect.
Note:
Never use a metal saw to cut
pipes because the sawdust may
enter the circuit.
When withdrawing the pipes, be
careful not to pinch them firmly
with pliers. The pipes may get
deformed.
Provide a protective sheet or a
steel plate so that the brazing
flame cannot influence
peripheries.
Be careful so as not to burn the
compressor terminals, the name
plate, the heat exchanger fin.
6
Heat up the brazed part
of the suction side and
disconnect it.
7
Lift the compressor up
and remove it.
Step
Procedure
Points
(R5308)
(R5309)
Содержание FTXS30LVJU
Страница 8: ...SiUS091133 Table of Contents vii...
Страница 11: ...SiUS091133 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 FTXS Series 2 1 2 FDXS Series 4...
Страница 15: ...SiUS091133 5 Specifications Part 2 Specifications 1 Specifications 6 1 1 FTXS Series 6 1 2 FDXS Series 11...
Страница 164: ...SiUS091133 Check Service Diagnosis 154 15 18 class 24 30 36 class Power module R16697 R16073 Power module...
Страница 259: ...Indoor Unit FTXS30 36LVJU SiUS091133 249 Removal Procedure 6 Disconnect the connector Step Procedure Points R9558...
Страница 413: ...Wiring Diagrams SiUS091133 403 Appendix...