Troubleshooting
SiUS091133
107
Service Diagnosis
4.7
Low-voltage Detection or Over-voltage Detection
Remote
Controller
Display
U2
Method of
Malfunction
Detection
Indoor Unit
The zero-cross detection of the power supply is evaluated by the indoor unit PCB.
Outdoor Unit
Low-voltage detection:
An abnormal voltage drop is detected by the DC voltage detection circuit.
Over-voltage detection:
An abnormal voltage rise is detected by the over-voltage detection circuit.
Malfunction
Decision
Conditions
Indoor Unit
There is no zero-cross detection in approximately 10 seconds.
Outdoor Unit
Low-voltage detection:
The voltage detected by the DC voltage detection circuit is below 150 ~ 200 V (depending on
the model).
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Over-voltage detection:
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer.
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Supposed
Causes
Supply voltage is not as specified.
Defective DC voltage detection circuit
Defective over-voltage detection circuit
Defective PAM control part
Disconnection of compressor harness
Noise
Momentary fall of voltage
Momentary power failure
Defective indoor unit PCB
Содержание FTXS30LVJU
Страница 8: ...SiUS091133 Table of Contents vii...
Страница 11: ...SiUS091133 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 FTXS Series 2 1 2 FDXS Series 4...
Страница 15: ...SiUS091133 5 Specifications Part 2 Specifications 1 Specifications 6 1 1 FTXS Series 6 1 2 FDXS Series 11...
Страница 164: ...SiUS091133 Check Service Diagnosis 154 15 18 class 24 30 36 class Power module R16697 R16073 Power module...
Страница 259: ...Indoor Unit FTXS30 36LVJU SiUS091133 249 Removal Procedure 6 Disconnect the connector Step Procedure Points R9558...
Страница 413: ...Wiring Diagrams SiUS091133 403 Appendix...