Troubleshooting
SiUS091133
123
Service Diagnosis
4.18 High Pressure Control in Cooling
Remote
Controller
Display
F6
Method of
Malfunction
Detection
High-pressure control (operation halt, frequency drop, etc.) is activated in cooling operation if the
temperature sensed by the outdoor heat exchanger thermistor exceeds the limit.
Malfunction
Decision
Conditions
The temperature sensed by the outdoor heat exchanger thermistor rises above about 60 ~ 65°C
(140 ~ 149°F).
The error is cleared when the temperature drops below about 50°C (122°F).
Supposed
Causes
The installation space is not large enough.
Dirty outdoor heat exchanger
Defective outdoor fan motor
Defective stop valve
Defective electronic expansion valve or coil
Defective outdoor heat exchanger thermistor
Defective outdoor unit PCB