SiUS091133
Forced Cooling Operation
Trial Operation and Field Settings
384
2. Forced Cooling Operation
Indoor Unit
Outdoor Unit
09/12 class
Item
Forced Cooling
Conditions
The forced cooling operation is allowed when both of the following conditions are
met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
Start
The forced cooling operation starts when any of the following conditions is fulfilled.
1) Press the forced cooling operation [ON/OFF] button (SW1) on the indoor unit
for 5 seconds.
2) Press the forced cooling operation [ON/OFF] button (SW1) on the outdoor unit.
Command
frequency
09/12 class: 58 Hz
15/18 class: 66 Hz
24 class: 31 Hz
30/36 class: 55 Hz
End
The forced cooling operation ends when any of the following conditions is fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation [ON/OFF] button (SW1) on the indoor unit
again.
3) Press the [ON/OFF] button on the remote controller.
4) Press the forced cooling operation [ON/OFF] button (SW1) on the outdoor unit.
Others
Protection functions have priority over all other functions during forced cooling
operation.
FTXS series
FDXS series
ON/OFF button (SW1)
(R14145)
[ON/OFF] button (SW1)
(R16615)
1
2
3
Push
Screwdriver
(R16614)
Forced cooling
operation
[ON/OFF] button
(SW1)
Содержание FTXS30LVJU
Страница 8: ...SiUS091133 Table of Contents vii...
Страница 11: ...SiUS091133 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 FTXS Series 2 1 2 FDXS Series 4...
Страница 15: ...SiUS091133 5 Specifications Part 2 Specifications 1 Specifications 6 1 1 FTXS Series 6 1 2 FDXS Series 11...
Страница 164: ...SiUS091133 Check Service Diagnosis 154 15 18 class 24 30 36 class Power module R16697 R16073 Power module...
Страница 259: ...Indoor Unit FTXS30 36LVJU SiUS091133 249 Removal Procedure 6 Disconnect the connector Step Procedure Points R9558...
Страница 413: ...Wiring Diagrams SiUS091133 403 Appendix...