2.8 Indoor unit main PCB
2.8.1 Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a power check of the indoor unit main PCB
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Turn ON the power of the unit.
2
Measure the voltage between the pins 1‑4 of the connector S300A on the
indoor unit main PCB.
Result:
The measured voltage MUST be 324 V DC.