SiUS041501E
Main Functions
Function and Control
26
1.4
Fan Speed Control for Indoor Unit
Outline
Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H, and HH.
The airflow rate can be automatically controlled depending on the difference between the room
thermistor temperature and the target temperature.
Automatic Fan
Speed Control
In automatic fan speed operation, the step SL is not available.
= The airflow rate is automatically controlled within this range when the
FAN
button is set to
automatic.
<Cooling>
The following drawing explains the principle of fan speed control for cooling.
*The upper limit is M tap in 30 minutes from the operation start.
<Heating>
In heating operation, the fan speed is regulated according to the indoor heat exchanger
temperature and the difference between the room thermistor temperature and the target
temperature.
Note:
The fan stops during defrost control.
COMFORT
AIRFLOW
Operation
The fan speed is controlled automatically within the following steps.
<Cooling>
L tap ~ MH tap (same as automatic)
<Heating>
L tap ~ M tap
The latest command has the priority between POWERFUL and COMFORT AIRFLOW.
Step
Cooling
Heating
LLL
LL
L
ML
M
MH
H
HH (POWERFUL)
(R11681)
(R6834)
(R21654)
Fan speed
+2.5°C (+4.5°F)
+1.5°C (+2.7°F)
+0.5°C (+0.9°F)
MH*
M
ML
L
+3°C (+5.4°F)
+2°C (+3.6°F)
+1°C (+1.8°F)
Room thermistor temperature – target temperature
Содержание FTKN09NMVJU
Страница 12: ...SiUS041501E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Страница 17: ...SiUS041501E Specifications 6 Part 2 Specifications 1 Specifications 7 1 1 Cooling Only 7 1 2 Heat Pump 11...
Страница 59: ...SiUS041501E Remote Controller 48 Part 5 Remote Controller 1 Cooling Only 49 2 Heat Pump 51...
Страница 65: ...SiUS041501E Service Diagnosis 54 5 13 Power Module Check 100...
Страница 132: ...Revision History Month Year Version Revised contents 03 2015 SiUS041501E First edition...