Check
SiUS041501E
95
Service Diagnosis
5.7
Inverter Analyzer Check
Check No.15
Characteristics
Inverter analyzer: RSUK0917C
If an abnormal stop occurs due to compressor startup failure or overcurrent output when using an
inverter unit, it is difficult to judge whether the stop is caused by the compressor failure or some
other failure (main PCB, power module, etc.). The inverter analyzer makes it possible to judge the
cause of trouble easily and securely. (Connect an inverter analyzer as a quasi-compressor instead
of compressor and check the output of the inverter.)
Operation Method
Step 1
Be sure to turn off the power.
Step 2
Install an inverter analyzer instead of a compressor.
Note:
Make sure the charged voltage of the built-in smoothing electrolytic capacitor drops to 10 VDC
or below before carrying out the service work.
Reference:
If the terminals of the compressor are not FASTON terminals (difficult to remove the wire on the
terminals), it is possible to connect wires available on site to the outdoor unit from output side of
PCB. (Do not connect them to the compressor at the same time, otherwise it may result in
incorrect detection.)
(R18322)
(1) Remove the terminals from
the compressor.
(2) Connect the terminals to the
terminals of the inverter
analyzer.
Compressor
Inverter analyzer
Be careful not to let the terminals (U, V,
W) touch each other. Otherwise, high
voltage is applied.
Содержание FTKN09NMVJU
Страница 12: ...SiUS041501E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Страница 17: ...SiUS041501E Specifications 6 Part 2 Specifications 1 Specifications 7 1 1 Cooling Only 7 1 2 Heat Pump 11...
Страница 59: ...SiUS041501E Remote Controller 48 Part 5 Remote Controller 1 Cooling Only 49 2 Heat Pump 51...
Страница 65: ...SiUS041501E Service Diagnosis 54 5 13 Power Module Check 100...
Страница 132: ...Revision History Month Year Version Revised contents 03 2015 SiUS041501E First edition...