SiUS041501E
Troubleshooting
Service Diagnosis
66
4.6
Low-voltage Detection or Over-voltage Detection
Error Code
U2
Method of Error
Detection
Low-voltage detection:
An abnormal voltage drop is detected by the DC voltage detection circuit.
Over-voltage detection:
An abnormal voltage rise is detected by the over-voltage detection circuit.
Error Decision
Conditions
Low-voltage detection:
The voltage detected by the DC voltage detection circuit is below 180 ~ 196 V (depending on
the model).
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Over-voltage detection:
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer (over
458 ~ 500 V, depending on the model).
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Supposed
Causes
Power supply voltage is not as specified.
Defective DC voltage detection circuit
Defective over-voltage detection circuit
Defective PAM control part
Disconnection of compressor harness
Short circuit inside the fan motor winding
Noise
Momentary drop of voltage
Momentary power failure
Defective outdoor unit PCB
Содержание FTKN09NMVJU
Страница 12: ...SiUS041501E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Страница 17: ...SiUS041501E Specifications 6 Part 2 Specifications 1 Specifications 7 1 1 Cooling Only 7 1 2 Heat Pump 11...
Страница 59: ...SiUS041501E Remote Controller 48 Part 5 Remote Controller 1 Cooling Only 49 2 Heat Pump 51...
Страница 65: ...SiUS041501E Service Diagnosis 54 5 13 Power Module Check 100...
Страница 132: ...Revision History Month Year Version Revised contents 03 2015 SiUS041501E First edition...