Main Functions
SiUS041501E
29
Function and Control
1.7
Thermostat Control
Outline
Thermostat control is based on the difference between the room thermistor temperature and the
target temperature.
Detail
Thermostat OFF Condition
The temperature difference is in the zone A.
Thermostat ON Conditions
The temperature difference returns to the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling: 10 minutes, Dry: 7.5 minutes, Heating: 10 seconds)
<Cooling / Dry>
<Heating>
Refer to Temperature Control on page 23 for detail.
B
A
OFF
ON
C
Room thermistor temperature – target temperature
–1.5˚C (–2.7˚F)
(R14663)
Cooling : –0.5˚C (–0.9˚F)
Dry : –0.5˚C (–0.9˚F)
Cooling : –2.0˚C (–3.6˚F)
Dry : –2.5 ~ –2.0˚C (–4.5 ~ –3.6˚F)
B
B
A
A
OFF
OFF
ON
ON
C
C
2.0˚C (3.6˚F)
0.5˚C (0.9˚F)
1.5˚C (2.7˚F)
Room thermistor temperature – target temperature
(R21656)