SiBE04-101
Troubleshooting
Service Diagnosis
89
4.3
Faulty PCB
Remote Controller
Display
A1
Indoor unit LED
Display
Method of
Malfunction
Detection
Evaluation of zero-cross detection of power supply by indoor unit.
Malfunction
Decision
Conditions
When there is no zero-cross detection in approximately 10 continuous seconds.
Supposed Causes
Faulty indoor unit PCB
Faulty connector connection
Troubleshooting
Note:
Connector numbers vary depending on models.
Control connector......S37
Connector connection check
(note).
YES
Is it normal?
NO
Correct connections.
Check of 12V voltage.
YES
Is it 20V or lower?
NO
12VDC abnormal.
Replace the indoor unit PCB(2).
EEPROM abnormal .
Replace the indoor unit PCB(1).
(R1169)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.