SiBE04-101
Troubleshooting
Service Diagnosis
93
4.6
Operation Halt Due to Fan Motor (AC Motor) or Related Abnormality (Floor /
Ceiling Suspended Dual Type).
Remote Controller
Display
A6
Indoor unit LED
Display
Method of
Malfunction
Detection
The rotation speed detected by the hall IC during fan motor operation is used to determine abnormal fan
motor operation.
Malfunction
Decision
Conditions
When the detected rotation speed is less than 50% of the H tap under maximum fan motor rotation
demand.
Supposed Causes
Operation halt due to short circuit inside the fan motor winding.
Operation halt due to breaking of wire inside the fan motor.
Operation halt due to breaking of the fan motor lead wires.
Operation halt due to faulty capacitor of the fan motor.
Detection error due to faulty indoor unit PCB (2).
Troubleshooting
Rotate the fan by hand.
Check hall IC
∗
1
Operate the fan.
Does it rotate?
NO
Does it rotate smoothly?
Is
there an output
between the pins 2 and 3,
rotating the fan motor
once by hand?
Is it at the rated voltage?
Is there conductivity?
NO
Check the capacitor's conductivity
Check the fan motor voltage.
(immediately after re-start)
Is it at the rated voltage?
Check the fan motor voltage.
∗
2
NO
Is
an output between
the pins 1 and 3
approximately
5~12V?
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
Replace the fan motor.
Replace the fan motor
∗
2 Measure the voltage between the
red and black lead wires of the fan
motor, and check if the maximum
voltage reaches the rated voltage.
Replace the indoor unit PCB (2).
Replace the fan motor.
Replace the indoor unit PCB (2)
Replace the capacitor.
(Replace the PCB (2).)
Replace the fan motor.
(R1172)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Replace the
indoor unit
PCB.
∗
1 Check the Hall IC, with the power ON, operation OFF, and the connector connected.
∗
2 Measure the voltage between the pins 1 and 6.
The connection of the Hall IC lead wire is as the following.
S7
1
2
3
Grey (Power supply)
Purple (Signals)
Blue (Grounding)
1
3
6
H4
H5
H6
White
Red
Black
SiBE04-101.book Page 93 Monday, October 15, 2001 3:08 PM