Troubleshooting
SiBE04-101
88
Service Diagnosis
4.2
Outdoor Units
4
: ON,
1
: OFF,
5
: Blinks
Green: Flashes when in normal condition
Red: OFF in normal condition
- : Not used for troubleshooting
∗
: Varies depending on the cases.
Note:
1. When a sensor error occurs, check the remote controller display to determine which sensor is
malfunctioning.
If the remote controller does not indicate the error type, conduct the following operation.
*Turn the power switch off and back on again. If the same LED indication appears again immediately
after the power is turned on, the fault is in the thermistor.
*If the above condition does not result, the fault is in the CT.
2. The indoor unit error indication may take the precedence in the remote controller display.
Outdoor Unit LED Indication
Indication on the
remote controller
Description of the Fault
Details of Fault
(Refer to the
indicated
page.)
Green
Red
A
1
2
3
4
5
3
3
3
3
∗
Outdoor unit in normal condition
(Conduct a diagnosis of the indoor unit.)
—
5
4
3
4
4
A5
Operation halt due to cooling high pressure control
100
5
4
3
4
3
E5
Stoppage by OL actuation/Melt-down by temperature fuse
102
5
3
4
4
3
E6
Operation halt due to compressor seizing.
104
5
4
4
4
4
E7
DC fan motor seizing
105
5
3
4
3
4
∗
or
E8
Operation halt due to detection of input overcurrent.
106
5
4
3
4
3
F3
Abnormal discharge pipe temperature.
101
5
4
4
3
3
H6
Operation halt due to faulty position detection sensor.
108
5
4
4
3
3
H8
Operation halt due to detection of CT abnormality.
109
5
4
4
3
3
H9
Operation halt due to outside air thermistor abnormality.
112
5
3
3
4
3
L5
Operation halt due to detection of output overcurrent.
110
5
4
4
3
3
J3
Operation halt due to discharge pipe thermistor abnormality, or
due to detection of disconnected discharge pipe thermistor.
112
5
4
4
3
3
J6
Operation halt due to outdoor unit heat exchanger thermistor
abnormality.
112
5
3
3
4
4
U0
Operation halt due to detection of insufficient gas.
113
5
4
3
3
4
U2
Stoppage by low voltage of the main circuit (LVP)
115
5
4
3
4
4
—
Operation halt due to peak cut, freeze protection function or
indoor unit icing protection.
(Conduct a
diagnosis of the
indoor unit.)
4
—
—
—
—
∗
Faulty outdoor unit PCB
116
3
—
—
—
—
∗
Faulty outdoor unit PCB or signal transmitting/receiving circuit.
117