18
|
Electrical installation
Installer and user reference guide
70
FHA-A(9)
Split system air conditioner
4P708119-1 – 2022.11
18.1.3 Specifications of standard wiring components
Component
Specification
Interconnection cable
(indoor↔outdoor)
Only use harmonized wire providing double insulation
and suitable for applicable voltage
4-core cable
Minimum size 2.5 mm²
User interface cable
Only use harmonized wire providing double insulation
and suitable for applicable voltage
2-core cable
Minimum size 0.75 mm²
Maximum length 500 m
18.2 To connect the electrical wiring to the indoor unit
NOTICE
▪
Follow the wiring diagram (delivered with the unit, located at the inside of the
service cover).
▪
For instructions on how to connect the optional equipment, see the installation
manual delivered with the optional equipment.
▪
Make sure the electrical wiring does NOT obstruct proper reattachment of the
service cover.
It is important to keep the power supply and the transmission wiring separated
from each other. In order to avoid any electrical interference the distance between
both wirings should ALWAYS be at least 50 mm.
NOTICE
Be sure to keep the power line and transmission line apart from each other.
Transmission wiring and power supply wiring may cross, but may NOT run parallel.
1
Remove the service cover.
2
Open the knockout hole and install the resin bushing (accessory). Refer to:
54].
50 mm
b c
a
d
c
a
Power supply wiring
b
Resin bushing (accessory)
c
Sealing material for gaps around pipes and cables (accessory)
d
User interface cable and transmission cable
3
Install the 2 wiring fixtures with screws for wiring fixture (accessory).