Piping installation
Installer and user reference guide
59
FHA-A(9)
Split system air conditioner
4P708119-1 – 2022.11
17 Piping installation
In this chapter
17.1 Preparing refrigerant piping
17.1.1 Refrigerant piping requirements
CAUTION
Piping MUST be installed according to instructions given in
59]. Only mechanical joints (e.g. braze+flare connections) that are
compliant with the latest version of ISO14903 can be used.
NOTICE
The piping and other pressure-containing parts shall be suitable for refrigerant. Use
phosphoric acid deoxidised seamless copper for refrigerant piping.
INFORMATION
Also read the precautions and requirements in the
7].
▪
Foreign materials inside pipes (including oils for fabrication) must be
≤30 mg/10 m.
Refrigerant piping diameter
For piping connection of the indoor unit, use the following piping diameters:
Pipe outer diameter (mm)
Class
Liquid pipe
Gas pipe
35
Ø6.4
Ø9.5
50+60
Ø6.4
Ø12.7
71~140
Ø9.5
Ø15.9
Refrigerant piping material
▪
Piping material:
phosphoric acid deoxidised seamless copper
▪
Flare connections:
Only use annealed material.
▪
Piping temper grade and thickness:
Содержание FHA100AVEB8