![Daikin FHA100AVEB8 Скачать руководство пользователя страница 55](http://html.mh-extra.com/html/daikin/fha100aveb8/fha100aveb8_user-reference-manual_2460428055.webp)
16
|
Unit installation
Installer and user reference guide
55
FHA-A(9)
Split system air conditioner
4P708119-1 – 2022.11
2
Remove the hanger bracket. Loosen the 2 hanger bracket installation bolts
(M8) on both sides (total 4 places) within 10 mm. Remove the fixing screw
(M5) from the rear hanger bracket and pull the hanger bracket backward in
the direction of the arrow in order to remove it.
a
c
b
b
b
d
c
10 mm
a
Hanger bracket fixing screw (M5)
b
Hanger bracket installation bolt (M8)
c
Hanger bracket
d
Indoor unit
CAUTION
Do NOT remove the (milky white) tape from the exterior of the indoor unit.
Removing the tape may cause an electric shock or a fire.
3
Fix the hanger bracket to the suspension bolts.
4
Lift up the indoor unit and slide it to the back. Fix the hanger bracket
installation bolt (M8) for temporary hanging. Do NOT hold the unit by the
reinforcing plate.
b
b
a
c
d
a
Hanger bracket
b
Hanger bracket installation bolt (M8)
c
Hanger bracket fixing screw (M5)
d
Reinforcing plate
5
Install the hanger bracket fixing screws (M5) on both sides back (2 screws in
total).
6
Fully tighten all hanger bracket installation bolts (M8) (4 screws in total).
7
Make sure the unit is level. Refer to
"16.2.1 Guidelines when installing the
16.2.2 Guidelines when installing the drain piping
Make sure condensation water can be evacuated properly. This involves:
▪