![Daikin FHA100AVEB8 Скачать руководство пользователя страница 53](http://html.mh-extra.com/html/daikin/fha100aveb8/fha100aveb8_user-reference-manual_2460428053.webp)
16
|
Unit installation
Installer and user reference guide
53
FHA-A(9)
Split system air conditioner
4P708119-1 – 2022.11
Front view
5
175
200
c
b
a
G
H
J
(mm)
Top (ceiling) view
(mm)
F
210
D
B:
260
30
163
E
189
87
C
A
B
k
l
d
j
e
A:
690
h
g
f1
g
f2
i
4×
A
B
C
D
E
F
G
H
J
FHA35+50
960
920
378
324
270
375
398
377
260
FHA60+71
1270
1230
533
479
425
530
553
532
415
FHA100~140
1590
1550
693
639
585
690
713
692
575
A
Unit dimension
B
Suspension bolt pitch
a
Rear left drain piping outlet hole
b
Rear wiring outlet location
c
Wall hole for rear piping outlet (
⌀
100 mm)
d
Top panel wiring outlet position
e
Discharge
f1
Nut (field supply)
f2
Double nut (field supply)
h
Hanger bracket
g
Washer for hanger bracket (accessory)
i
Suspension bolt
j
Top panel drain piping connection position
k
Top panel gas side piping connection position
l
Top panel liquid side piping connection positions
▪
Level.
Use the level to make sure the unit is installed horizontally. If possible,
install the unit so the drain piping side is slightly tilted (maximum 1°)
A
B
A/B
B
A
≤
1°
≤
1°
≤
1°
A
Drain piping tilted to the right, or to the right and back
B
Drain piping tilted to the left, or to the left and back