![Daikin FHA100AVEB8 Скачать руководство пользователя страница 69](http://html.mh-extra.com/html/daikin/fha100aveb8/fha100aveb8_user-reference-manual_2460428069.webp)
18
|
Electrical installation
Installer and user reference guide
69
FHA-A(9)
Split system air conditioner
4P708119-1 – 2022.11
Use the following methods for installing wires:
Wire type
Installation method
Single-core wire
Or
Stranded conductor wire
twisted to "solid-like"
connection
c b
c
a
a
A
AA´
A´
a
Curled wire (single-core or twisted stranded
conductor wire)
b
Screw
c
Flat washer
Stranded conductor wire
with round crimp-style
terminal
c b
b
a
c
a
B
B
a
Terminal
b
Screw
c
Flat washer
Allowed
NOT allowed
Tightening torques
Wiring
Screw size
Tightening torque
(N•m)
Interconnection cable
(indoor↔outdoor)
M4
1.33~1.61
User interface cable
M3.5
0.79~0.97
▪
The earth wire between the wire retainer and the terminal must be longer than
the other wires.
1-3