18
OPERATING RANGE
OVERALL CHECKING
Outdoor
DB (°C)
54
52
19
14
19
23
Indoor WB (°C)
DB = Dry Bulb
WB = Wet Bulb
Ensure the following, in particular:-
1) The unit is mounted solidly and rigid in position.
2) Piping and connections are leak proof after charging.
3) Proper wiring has been done.
Drainage check:- Pour some water into left side of drain pan
(drainage are in right side of unit).
Test run:
1) Conduct a test run after water drainage test and gas leakage
test.
•
2) Watch out for the following:-
a) Is the electric plug firmly inserted into the socket?
b) Is there any abnormal sound from unit?
c) Is there smooth drainage of water?
Check that:
Condenser fan is running, with warm air blowing off the
condensing unit.
Evaporator blower is running and discharge cool air.
The remote controller incorporates a 3 minute delay in the
circuit. Thus, it requires about 3 minutes before the outdoor
condensing unit can start up.
•
1.
2.
3.
COOLING
PHASE SEQUENTIAL (3PH)
The unit with Scroll Compressor can only rotate in one direction. For this reason, a protective device (phase sequential) is fitted
to prevent incorrect wiring of the electrical phases. When the three phases are not connected correctly, the phase sequential
operates, and the unit will not start. This device is located in the control box of the outdoor unit.
The following table shows the LED indicator light for phase sequential under normal operation and fault conditions.
LED
Description
PW
(Red)
P_S
(Yellow)
P_T
(Yellow)
Actions
Normal operation
-
Reverse phase
Switch off the unit. Check the 3 phase wiring.
T phase missing
Switch off the unit. Check the 3 phase wiring.
S phase missing
Switch off the unit. Check the 3 phase wiring.
R phase missing
Switch off the unit. Check the 3 phase wiring.
Overheat
High discharge temperature. Check the refrigerant system.
High Pressure
High discharge pressure. Check the refrigerant system.
Low Pressure
Low suction pressure. Check the refrigerant system.
Sensor missing
Switch off the unit. Plug in sensor.
ON
OFF
Fast Blink
Outdoor
DB (°C)
52
50
19
14
19
23
Indoor WB (°C)
**Applicable only for RR20AV1KRE,
RR25AV1KRE, RR30AV1KRE, RR50A and RR60A
1-IM-5CC(HA)-1115(9)-DAIKIN-EN.i18 18
1-IM-5CC(HA)-1115(9)-DAIKIN-EN.i18 18
6/10/21 12:38:08 PM
6/10/21 12:38:08 PM
Содержание FDMRN20AV1K
Страница 23: ...CVR IM 5CC HA 1115 9 DAIKIN EN3 3 CVR IM 5CC HA 1115 9 DAIKIN EN3 3 6 10 21 12 39 03 PM 6 10 21 12 39 03 PM...
Страница 26: ...CVR IM 5CC HA 1115 9 DAIKIN AR3 3 CVR IM 5CC HA 1115 9 DAIKIN AR3 3 6 10 21 1 15 18 PM 6 10 21 1 15 18 PM...
Страница 38: ...2000 0 IM 5CC HA 1115 9 DAIKIN AR i9 9 0 IM 5CC HA 1115 9 DAIKIN AR i9 9 6 10 21 1 11 58 PM 6 10 21 1 11 58 PM...
Страница 47: ...CVR IM 5CC HA 1115 9 DAIKIN AR2 2 CVR IM 5CC HA 1115 9 DAIKIN AR2 2 6 10 21 1 15 18 PM 6 10 21 1 15 18 PM...