8
The drain pipe must be installed as shown in the diagram (see diagram above) to avoid damage caused by leaks and
condensation.
For the best result, keep the piping as short as possible. Slant the piping at an angle to improve the flow.
Ensure the drain pipe is securely insulated.
It is necessary to provide a drain trap in the drain outlet to relieve pressure that exists within the unit compared to the outside
atmospheric pressure when the unit is operating. The drain trap is to avoid possibility of splashes or an odor.
Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.
Conduct a water drainage test after the installation is completed. Make sure that the drainage flow is smooth.
In humid environments, use an extra drain pan to cover the entire area of the indoor unit.
•
•
•
•
•
•
•
Ceiling Concealed Drain Piping Work
Unit : mm
10 mm (0.39")
Bottom of
the unit
Insulate securely
100
100
Drain trap
or more
or more
Do not leave in water
S
la
n
t
UNIT DRAIN PIPE KI
UNIT DRAIN PIPE KA
UNIT SIDE VIEW
UNIT DRAIN PIPE KI
UNIT DRAIN PIPE KA
FIGURE 1
FIGURE 2
CABLE TIE
JOINT KA
F JOINT
JOINT KI
Connect Joint KA and Joint KI to unit drain pipe KA and unit drain pipe KI as Figure 1.
Ensure Joint KA and Joint KI is completely inserted to unit drain pipe.
Connect F Joint to Joint KA and Joint KI as Figure 1.
Ensure F Joint is completely inserted into Joint KA and Joint KI.
Connect drain piping to F Joint as Figure 2.
Tie cable tie firmly at all connecting points as Figure 2.
After fitting cable ties, it's advisable to insulate the Drain Joints and F Joint.
1)
2)
3)
4)
5)
DRAIN PIPING
DRAIN JOINT PIPE INSTALLATION PROCEDURE:
FOR 20A/25A/30A/36A/50A MODEL
SEE DETAIL A
DETAIL A
TO UNIT
JOINT KI
JOINT KA
1-IM-5CC(HA)-1115(9)-DAIKIN-EN.i8 8
1-IM-5CC(HA)-1115(9)-DAIKIN-EN.i8 8
6/10/21 12:38:06 PM
6/10/21 12:38:06 PM
Содержание FDMRN20AV1K
Страница 23: ...CVR IM 5CC HA 1115 9 DAIKIN EN3 3 CVR IM 5CC HA 1115 9 DAIKIN EN3 3 6 10 21 12 39 03 PM 6 10 21 12 39 03 PM...
Страница 26: ...CVR IM 5CC HA 1115 9 DAIKIN AR3 3 CVR IM 5CC HA 1115 9 DAIKIN AR3 3 6 10 21 1 15 18 PM 6 10 21 1 15 18 PM...
Страница 38: ...2000 0 IM 5CC HA 1115 9 DAIKIN AR i9 9 0 IM 5CC HA 1115 9 DAIKIN AR i9 9 6 10 21 1 11 58 PM 6 10 21 1 11 58 PM...
Страница 47: ...CVR IM 5CC HA 1115 9 DAIKIN AR2 2 CVR IM 5CC HA 1115 9 DAIKIN AR2 2 6 10 21 1 15 18 PM 6 10 21 1 15 18 PM...