6
INSTALLATION DIAGRAM
INSTALLATION OF THE INDOOR UNIT
Supply Duct
Air Intake
Wrap the insulated pipe with the
finishing tape from bottom to top
Air Intake
Outdoor Unit
Return Duct
Hanger
Air Discharge
Drain Piping
Thermal Insulation
Indoor Unit
The indoor unit must be installed such that there is no short
circuit of the cool discharge. Respect the installation clearance.
Do not put the indoor unit where there is direct sunlight on unit.
The location is suitable for piping and drainage and it must have
a large distance between a door and unit.
In cases where the temperature above the ceiling might reach
30°C or the humidity RH80%, reinforce the drain pan insulation
(10mm or thicker) or adding secondary Drain Pan. Condensation
may form on the surface of the insulating material.
Ceiling Concealed Mounting
Use the hanger supplied with the unit.
Make sure that the ceiling is sufficiently strong to withstand
the weight.
•
•
Field supply
Washer for hanger bracket
(attached)
Tighten
Detail A
See Detail A
Air inlet side
Air outlet side
Aluminium tape
(field supply)
Insulation material
(field supply)
Aluminium tape
(field supply)
1-IM-5CC(HA)-1115(9)-DAIKIN-EN.i6 6
1-IM-5CC(HA)-1115(9)-DAIKIN-EN.i6 6
6/10/21 12:38:06 PM
6/10/21 12:38:06 PM
Содержание FDMRN20AV1K
Страница 23: ...CVR IM 5CC HA 1115 9 DAIKIN EN3 3 CVR IM 5CC HA 1115 9 DAIKIN EN3 3 6 10 21 12 39 03 PM 6 10 21 12 39 03 PM...
Страница 26: ...CVR IM 5CC HA 1115 9 DAIKIN AR3 3 CVR IM 5CC HA 1115 9 DAIKIN AR3 3 6 10 21 1 15 18 PM 6 10 21 1 15 18 PM...
Страница 38: ...2000 0 IM 5CC HA 1115 9 DAIKIN AR i9 9 0 IM 5CC HA 1115 9 DAIKIN AR i9 9 6 10 21 1 11 58 PM 6 10 21 1 11 58 PM...
Страница 47: ...CVR IM 5CC HA 1115 9 DAIKIN AR2 2 CVR IM 5CC HA 1115 9 DAIKIN AR2 2 6 10 21 1 15 18 PM 6 10 21 1 15 18 PM...